Params. & Display
LoadController
Adaption
StartAdaption
AdaptionLoad
The burner and boiler must be ready for 10 min. run, where boiler temperature or
pressure is dropped to 5 % below set value, and then run with full load. This occurs
automatically according to the following diagram. Boiler load should stay constant
throughout adaptation.
Flow chart_WD capacity ver. 3
O
2
trim control must not be active during adaptation.
In the WD200 system, deactivate O
2
trim control from the operating and display unit
menu:
Operation
O2Ctrl activate
deactivated
activated
M4248 2316EN
73 (114)