Brine 0 °C / –3 °C and water 30 °C / 35 °C (B0/W35)
MODEL / RATED OUTPUT (kW)
3~ 400 V, 50 Hz, PE
WATER AND ETHANOL
SOLUTION, 30 m-% OF ETHANOL
6
8
10
13
17
21
Brine temperature difference
°C 3
3
3
3
3
3
Brine flow rate (total)
kg/s 0.35 0.47 0.64 0.81 1.08 1.35
Brine flow rate (total)
L/s 0.36 0.48 0.66 0.84 1.12 1.40
Brine flow rate (total)
m3/h 1.31 1.74 2.39 3.03 4.03 5.05
Pump head
m 7.6
6.8
7.5
5.7
11.9 11.1
Internal pressure loss
ECO
kPa 14
16
18
21
19
29
CUBE
kPa 16
19
23
28
-
-
Internal pressure loss expressed in terms of pump
head
ECO
m 1.5
1.7
1.9
2.2
2.1
3.1
CUBE
m 1.7
2.0
2.5
3.0
-
-
Pump head for external pressure loss
ECO
m 6.1
5.1
5.6
3.5
9.8
8.0
CUBE
m 5.9
4.8
5.0
2.7
-
-
Brine 0 °C / –4 °C and water 30 °C / 35 °C (B0/W35)
MODEL / RATED OUTPUT (kW)
3~ 400 V, 50 Hz, PE
WATER AND ETHANOL
SOLUTION, 30 m-% OF ETHANOL
6
8
10
13
17
21
Brine temperature difference
°C 4
4
4
4
4
4
Brine flow rate (total)
kg/s 0.26 0.35 0.48 0.61 0.81 1.02
Brine flow rate (total)
L/s 0.27 0.36 0.50 0.63 0.84 1.05
Brine flow rate (total)
m3/h 0.98 1.31 1.79 2.27 3.02 3.78
Pump head, standard pump
m 7.6
7.6
8.2
7.4
11.8 11.9
Pump head for pumps delivered on special order
m 9.2
9.3
11.4 11.7
Internal pressure loss
ECO
kPa 9
10
11
20
12
17
CUBE
kPa 10
12
15
17
Internal pressure loss expressed in terms of pump
head
ECO
m 1.0
1.1
1.2
2.2
1.3
1.8
CUBE
m 1.1
1.2
1.5
1.8
-
-
Pump head for external pressure loss
ECO
m 6.6
6.5
7.0
5.2
10.5 10.1
CUBE
m 6.5
6.4
6.7
5.6
-
-
6.6 Operating conditions
The unit’s operating condition range is provided below. The unit has
been designed for use within the specified conditions. The unit’s
performance cannot be guaranteed outside the recommended
conditions.
52 (59)
M8006 2314EN