Model/rated capacity
3~, 400 V, 50 Hz, PE
6
8
10
13
17
21
Compressor heating
only, in-line heater
disabled or not installed
3 x
10 A
10 A
16 A
16 A
20 A
20 A
Heating by either
compressor or in-line
heater, simultaneous
use disabled
3 x
16 A
16 A
16 A
16 A
20 A
20 A
Simultaneous use of
compressor and in-line
heater enabled
3 x
16 A
16 A
20 A
20A
25 A
25 A
The indicated fuse rating is given for the brine pump, the condenser
pump, and the circulation pump for one heating circuit.
CUBE
MODEL / RATED CAPACITY (kW)
3~ 400 V, 50 Hz, PE
6
8
10
13
Dimensions and weight
Width
mm
599
599
599
599
Depth
mm
626
626
626
626
Height (frame)
mm
1910
1910
1910
1910
Empty weight
kg
242
244
245
256
In-line heater
Internal in-line heater as standard
yes
yes
yes
yes
Heater output
kW
6
6
6
6
Heater power stages
pcs
3
3
3
3
Output for each heater stage
kW
2
2
2
2
Soft starter
Soft starter as standard
yes
yes
yes
yes
Pipe connections
Condenser circuit connection (copper pipe)
mm
28
28
28
28
Brine circuit connection (copper pipe)
mm
28
28
28
28
Maximum permissible operating pressure
bar
3
3
3
3
Noise level
A-weighted sound pressure level
At 1 m distance
dB (A)
< 40
< 40
< 40
< 40
Fuse
Heating by either compressor or in-
line heater, simultaneous use disabled
3 x
16 A
16 A
16 A
16 A
Simultaneous use of compressor
and in-line heater enabled
3 x
16 A
20 A
20 A
25 A
The indicated fuse rating is given for the brine pump, the condenser
pump, and the circulation pump for one heating circuit.
M8006 2314EN
47 (59)