Electrical connection
1 Air vent valve
9.5 Heating circuit with mixing valve
To use the indoor unit with a heating circuit with mixing
valve, the internal heating circulation pump must be re-
placed with an adaptor.
1 Internal heating circulation pump
►
The adaptor needs to have the following dimensions:
-
Connections 2 x 1½” MT, with flat gasket
- Length 180 mm
- Nominal diameter DN 25 (1”)
►
The adaptor is available from OCHSNER as an
accessory.
Subsequently, the heating circuit can be set up externally.
Connect the components of the heating circuit with mixing
valve to the following connections in the control box:
Components
Connections
Mixing valve
MIV-HK2
Mixed circuit sensor
T-HK2
Mixing circuit circulation pump
PUM-HK2
Note
If these conversions are carried out after commis-
sioning, the system must then be recommissioned.
Commissioning is carried out by OCHSNER cus-
tomer service or by a customer service partner
authorised by OCHSNER.
10. Electrical connection
10.1 General
WARNING: Electrocution
Before commencing electrical connection and
installation work, the heat pump system must be
isolated from the power supply.
WARNING: Electrocution
Work on electrical connections and installation may
only be conducted by qualified contractors.
WARNING: Electrocution
Before commissioning, the necessary fault pro-
tection measures on the system and the earth
connection must be checked by a qualified con
-
tractor.
»
Before commencing work to connect up the power
supply, the necessary activities defined in section
“Preparing the electrical connections” must have
been completed.
»
For the electrical connection, use the system princi-
ple schematic appropriate to your heat pump system.
(See page 58, System principle schematic)
10.2 Electrical connection of the indoor unit
»
Remove the appliance cladding. (See page 33,
Disassembling the appliance casing)
Note
When fitting the cables in the indoor unit, ensure
that subsequent connection work and soldering on
the refrigerant pipes will not be obstructed by the
cables.
Note
For the shielded cables between the outdoor and
indoor units, use the shielding clamps provided on
the control box panel.
Note
For the cables inside the control box on the indoor
unit, use the cable strain relief fittings provided.
Observe the permissible torque. (0.5-0.8 Nm)
Summary of Contents for AIR FALCON 212 C11A T200
Page 2: ...2 www ochsner com PIA 982043 AIR FALCON T200 ih EN...
Page 7: ...PIA 982043 AIR FALCON T200 sh EN www ochsner com 7 Safety...
Page 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Page 13: ...00_200_202_08_02_002 EN www ochsner com 13 Device description...
Page 31: ...00_200_202_08_01_002 EN www ochsner com 31...
Page 47: ...PIA 982043 AIR FALCON T200 in EN www ochsner com 47...
Page 51: ...00_400_01_01 EN www ochsner com 51...
Page 65: ...PIA 982043 AIR FALCON T200 td EN www ochsner com 65...
Page 67: ...PIA_982043_AIR_FALCON_T200_EN06 1 www ochsner com 67...