Steam Generator Manual

12.   Maintenance

The single biggest problem with steam generation is the build up of scale resulting from dissolved 

solids within the water. Scaling can cause the elements to fail, the water level sensors not to 

function, premature failure of the O-rings resulting in leaks from around the elements. The extent 

of the problem will vary according to the degree of hardness in the local water supply.

For all commercial operators we recommend the use of a water softener.

Expect 2500 hours element life, this can be serious depleted by poor maintenance.  

All users commercial and domestic must ensure a regular maintenance routine to descale 

the generator – the frequency of this will vary according to the degree of hardness in the 

local water supply and the amount of time the generator is used for. Check the water for 

hardness and arrange the descaling routine accordingly: - 

High levels of hardness descale once every 50 to 100 hours of operation.

Medium levels of hardness descale once every 100 to 250 hours operation.

Low levels of hardness descale once every 250 to 1000 hours of operation.

To descale the generator use a solution of weak acid crystals (such as citric acid) mixed with water 

Citric acid can be purchased from:

www.thebathingplace.com

www.oceanic-saunas.eu 

12.1.  Descaling procedure

i.  Firstly push the drain button to empty the tank, check the valve is draining. Once the machine 

has finished draining isolate the mains power.

ii.  Unscrew the top plate of the machine which says water level probe, disconnect the probes 

wires with a flat screw driver and pull the probe out.

iii.  Fill the machine using a funnel with 5-6 litres of pre mixed citric acid.

iv.  Replace the probe and reconnect.

v.  Heat the machine for 2 minutes.

vi.  Leave the machine for 4 hours minimum

vii.  Drain 2-3 times.

Follow the instruction supplied with the crystals and allow sufficient time for the solution to 

dissolve the scale before flushing out the generator. For best results add to water, steam for two 

minutes then leave overnight. Empty the next days and flush twice using drain cycle. 

Faults arising from a result of a failure to descale the generator are not covered by warranty.

Because heating and cooling cause expansion and contraction it is important to inspect all the 

water and steam inlets and outlets as well as their pipes and connectors on a regular basis to 

ensure there are no leaks.

Clean the filter net in the magnetic valve according to the water quality in the location.

The condition of the wiring and electrical integrity of the generator should be checked regularly - 

for commercial operators this should be at least once a year. 

Summary of Contents for OC-105 S

Page 1: ...Oceanic Ltd Pountney Street Wolverhampton WV2 4HX Phone 01902 450 550 sales oceanic saunas co uk www oceanic saunas co uk Sauna Steam STEAM GENERATOR Domestic Light Commercial Assembly and operating m...

Page 2: ...e 2 OC A Controller Parameters 8 5 7 Temperature Sensor Parameters 8 6 OC A Controller Description 9 7 Installation 10 7 1 Generator Size 10 7 2 Steam Generator Location 11 7 3 Water and Steam Connect...

Page 3: ...your steam generator 1 or 3 phase For hard water areas please read our descaling section on page Water supply must have maximum of 1 bar pressure recommend the use of a pressure reducing valve if nec...

Page 4: ...omestic OC 40 4 17A 390 190 335 1 2 1 2 1 2 White OC 60 6 26A 8 6A 390 190 335 1 2 1 2 1 2 White OC 80 8 35A 11 6A 450 190 353 3 4 1 2 1 2 Chrome Steam On Demand OC 60 S 6 26 8 6 390 190 335 15 1 2 1...

Page 5: ...rol two or more steam generators e g if you need a 24KW steam generator you can use one OC A controller to control two 12kw steam generator or three 10kw steam generators Temperature sensor OC A contr...

Page 6: ...45 72 60 OC 80 90 450 195 353 35 135 45 72 60 OC 10 120 390 206 353 25 135 45 77 60 5 2 Steam Generator Frame Sizes 5 3 Clearance distances 5 4 Ventilation Ensure air flow into area where steam gener...

Page 7: ...Boiler 6 Insulation material Reduce the loss of the boiler heat 7 Water lever probe Detect the water level 8 Steam outlet Steam outlet 9 Pressure relief valve Operates if the pressure in the boiler ex...

Page 8: ...x 22 When the time window displays Long the generator will operate continuously until it is switched off MODEL Detected Scope Max Cut out Temperature Size mm o C o F o C o F L W H OC S 0 110 32 230 60...

Page 9: ...is filling green water level OK Note if the LED remains red in excess of 5 minutes check water supply 12 L3 Indicator LED for drain red for draining green for draining and filling at the same time 13...

Page 10: ...r and cause a blockage I e the pipe must not go down and then up There must be no valve or other blockage in the steam pipe The steam pipe should be metal of other material that can endure 150 C tempe...

Page 11: ...holes in the back plate Then with the front cover removed fix the 3rd screw to secure the unit in place 10m The steam generator can be installed anywhere that is dry and has an airflow Example locati...

Page 12: ...er supply using a flexible hose with 1 2 inch fittings iii Steam outlet 1 2 inch or 3 4 inch use the same dimension copper pipe to connect it if the steam pipe is longer than 5 meter it should be insu...

Page 13: ...rom the steam outlet Use a 4mm screw fix it in place and then connect to the wire from the controller vi Fix protective cover supplied over the temperature Temperature Sensor 4mm Screw Cover to protec...

Page 14: ...operators may wish to take advantage of the steam on demand function which will allow customers to press the steam on demand button located outside the steam room after which the generator will opera...

Page 15: ...Sauna Steam Oceanic Saunas 01902 450 550 sales oceanic saunas co uk 15 Steam Generator Manual...

Page 16: ...es the factory the default settings are 40o and 1 hour of operation these can be adjusted as follows i Time setting press set key the time display window will flash press to adjust the time every pres...

Page 17: ...main circuit board the transformer has failed or has a loose connection Control panel lit up but no steam Water probe Control lead connection Water supply 1 If L2 is green L7 is yellow remove the wat...

Page 18: ...d mixed with water Citric acid can be purchased from www thebathingplace com www oceanic saunas eu 12 1 Descaling procedure i Firstly push the drain button to empty the tank check the valve is drainin...

Page 19: ...trical elements and failures resulting from misuse or abuse such as a failure to descale as explained previously If you are using the generator for more than 20 hours a week in a hard water area witho...

Reviews: