2.SPECIFICATION

2.1 Performance data of Swimming Pool Heat  Pump Unit

*** REFRIGERANT :  R32

Rated Heating: Outdoor air temp: 27

, Inlet water temp:26

/28

                

/24.3

UNIT

By 50Hz

Range

Nominal  Heating PowerInput 

By 50Hz

Range

Nominal Running Current Input 

By 50Hz

Range

Power Supply

Compressor Quantity

Compressor

Fan Quantity

Fan Power Input

Fan Rotate Speed

Fan Direction

Noise

Water Connection

Water Flow Volume

Water Pressure Drop(max)

Unit Net Dimensions(L/W/H)

Unit Ship Dimensions(L/W/H)

Net Weight

Shipping Weight 

  

Nominal  Heating Capacity

kW

Btu/h

kW

Btu/h

kW

kW

A

A

 

 

 

 

W

RPM

 

dB(A)

mm

3

m /h

kPa

mm

mm

kg

kg

                              

Oasis I9

9.00

30600

2.20

9.00

7480

30600

1.60

 

0.16

1.60

7.0

 

0.8

7.0

230V

/50Hz

1

rotary

1

100

400-800

horizontal

39-51

40

3.0

4.0

1000

×

418

×

605

1030

×

435

×

615

45

54

Oasis I12

12.00

40800

2.90

12.00

9860

40800

2.12

 

0.21

2.12

9.4

 

1.1

9.4

230V

/50Hz

1

rotary

1

100

400-800

horizontal

42-53

40

3.7

4.5

1000

×

418

×

605

1030

×

435

×

615

46

68

1. The unit can only be repaired by qualified installer centre personnel or an authorised 
     dealer.

for Europe market

2. This appliance is not intended for use by persons (including children) with reduced physical
    sensory or mental capabilities, or lack of experience and knowledge, unless they have been
    given supervision or instruction concerning use of the appliance by a person responsible for 
    their safety. 

for Europe market

    Children should be supervised to ensure that they do not play with the appliance.
3. Please make sure that the unit and power connection have good earthing, otherwise may 
    cause electrical shock.
4. If the supply cord is damaged, it must be replaced by the manufacturer or our service agent
    or similarly qualified person in order to avoid a hazard.
5. Directive 2002/96/EC (WEEE): 
    The symbol depicting a crossed-out waste bin that is underneath the appliance indicates 
    that this product, at the end of its useful life, must be handled separately from domestic
    waste, must be taken to a recycling centre for electric and electronic devices or handed 
    back to the dealer when purchasing an equivalent appliance. 
6. Directive 2002/95/EC (RoHs): This product is compliant with directive 2002/95/EC (RoHs) 
    concerning restrictions for the use of harmful substances in electric and electronic devices.
7. The unit CANNOT be installed near the flammable gas. Once there is any leakage of the gas
     , fire can be occur.
8. Make sure that there is circuit breaker for the unit, lack of circuit breaker  can lead to 
    electrical shock or fire.
9. The heat pump located inside the unit is equipped with an over-load protection system. It 
    does not allow for the unit to start for at least 3 minutes from a previous stoppage.
10. The unit can only be repaired by the qualified personnel of an installer center or an 
     authorized dealer. 

for North America market

11. Installation must be performed in accordance with the NEC/CEC by authorized person only.
    

for North America market

12. USE SUPPLY WIRES SUITABLE FOR 75

.

13. Caution: Single wall heat exchanger, not suitable for potable water connection.

 Caution & Warning

1. PREFACE

3

Summary of Contents for I19

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Page 2: ......

Page 3: ...ch 4 5 4 6 4 7 Silent 4 8 4 9 4 10 4 11 Main board 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Parameter list and breakdown table Cable specific...

Page 4: ...mming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Dur...

Page 5: ...The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Applia...

Page 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Page 7: ...oise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight Nominal Heating Capacity kW Btu h kW Btu h kW kW A A W R...

Page 8: ...antity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net...

Page 9: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Modles Oasis I9 Oasis I12 unit mm 2 SPECIFICATION 6 545 956 1000 398...

Page 10: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Models Oasis I19 unit mm 2 SPECIFICATION 7 Water inlet 40 Water outlet 40 96 790 490 862 466 1115 1160 467...

Page 11: ...teps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary t...

Page 12: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Page 13: ...o the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand a...

Page 14: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Page 15: ...ed to enter and exit the mute mode with one click 4 2 Key and icon function instruction Key symbols It is used to switch the unit mode temperature setting and parameter setting It is used to carry out...

Page 16: ...the unit It will display when compressor is started It will display when water pump is started It will display when fan is started When the timing mute function is started it keeps bright for a long...

Page 17: ...shut down the wire controller will display as follows Operations are the same as under ON OFF main interface 4 4 Mode switch Under the main interface Short press to switch the unit among heating cooli...

Page 18: ...When the unit is under the defrosting state the defrosting symbol is on with the display interface as follows Notes 1 After completing the defrosting the unit will be automatically switched to the hea...

Page 19: ...erating steps the changes will not be saved and return to the main interface Under the clock setting interface Long press for 2 s to enter into the system times setting interface Short press Press or...

Page 20: ...interface Notes 1 Under the Timer ON OFF setting interface if there is no operation for 20 s the system will automatically memorize user s settings and return to the main interface 2 Under the Timer O...

Page 21: ...p long press of for 2 s Short press or Short press for entering the hour digit setting of timing on silent Short press or Short press for confirming the timing on silent and turn to the setting of tim...

Page 22: ...nd the screen will be lighten after other operations conducted 2 Under the OFF interface locking operation is available and the operation method is the same as locking screen under the ON interface 2...

Page 23: ...sor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and cold circuit check and replace this temp sensor Check whether fan motor is broken or locked...

Page 24: ...nt Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Check the communication connection Check the PFC switch tube short circuit or not Ch...

Page 25: ...n Instruction 10 2 Parameter list Meaning 28 28 27 Remarks Adjustable Adjustable Adjustable Default Refrigeration target temperature set point Heating the target temperature set point Automatic target...

Page 26: ...23 Controller interface diagram and definition 4 11 Main board Oasis I9 I12 4 Use and Operation Instruction 1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 1 2 ACN1 ACL1...

Page 27: ...1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 Controller interface diagram and definition 4 11 Main board Oasis I19 24 4 Use and Operation Instruction 1 2...

Page 28: ...put Water output temperature input System fan coil temperature input Ambient temperature input System Exhaust temperature input Earth wire Earth wire System suction temperature input Water input tempe...

Page 29: ...Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shall b...

Page 30: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Page 31: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Page 32: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Page 33: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Page 34: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Page 35: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Page 36: ...33 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I9 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 37: ...e switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat ex...

Page 38: ...35 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I12 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 39: ...re switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat e...

Page 40: ...6 APPENDIX 6 3 Explosive view of the unit 37 Moddel Oasis I19 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 41: ...Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat exchanger...

Page 42: ...Note...

Page 43: ......

Page 44: ...Code 20190508 0001...

Reviews: