6.APPENDIX

32

6.2 Comparison table of refrigerant saturation temperature

Pressure

(MPa )

Temperature

(R410A)(

)

Pressure

(MPa )

Temperature

(R32)(

)

Temperature

(R410A)(

)

Temperature

(R32)(

)

0        0.3     0.5      0.8       1       1.3      1.5     1.8        2        2.3 

2.5      2.8      3         3.3     3.5      3.8       4       4.5        5        5.5 

-51.3    -20       -9         4       11       19       24       31       35       39

-52.5    -20      -9        3.5     10        18      23      29.5   33.3    38.7

  43       47        51      55        57       61      64       70      74       80

  42      46.5   49.5   53.5      56       60      62      67.5   72.5    77.4

6.APPENDIX

31

6.1 Cable  specification

When the unit will be installed at outdoor, please use the cable which can against UV.

(1) 

  

Single phase unit

10~16A
16~25A
25~32A
32~40A
40 ~63A

63~75A
75~101A
101~123A
123~148A
148~186A
186~224A

Phase line

MCB

Creepage protector

Signal line

2

×

n

0.5mm

Nameplate 

maximum 

current

Earth line

No  more 
than 10A

2

2

×

1.5mm

2

2

×

2.5mm

2

2

×

4mm

2

2

×

6mm

2

2

×

10mm

2

2

×

16mm

2

2

×

25mm

2

2

×

25mm

2

2

×

35mm

2

2

×

50mm

2

2

×

70mm

2

2

×

95mm

20A
32A

40A

40A

63A
80A

100A

125A

160A

225A

250A

280A

2

1.5mm

2

2.5mm

2

4mm

2

6

mm

2

10mm

2

16mm

2

mm

25

2

mm

25

2

35mm

2

50mm

2

70mm

2

95mm

30mA less than 0.1 sec

10~16A

16~25A
25~32A
32~40A
40 ~63A

63~75A

75~101A

101~123A

123~148A

148~186A

186~224A

Phase line

MCB

Creepage protector

Signal line

2

×

n

0.5mm

Nameplate 

maximum 

current

Earth line

No  more 
than 10A

20A
32A
40A
40A

63A
80A

100A

125A

160A

225A

250A

280A

2

1.5mm

2

2.5mm

2

4mm

2

6

mm

2

10mm

2

16mm

2

mm

25

2

mm

25

2

35mm

2

50mm

2

70mm

2

95mm

(2) Three

  

 phase unit

2

3

×

1.5mm

2

3

×

2.5mm

2

3

×

4mm

2

3

×

6mm

2

3

×

10mm

2

×

16mm

3

2

×

25mm

3

2

3

×

25mm

2

3

×

35mm

2

3

×

50mm

2

3

×

70mm

2

3

×

95mm

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec
30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec
30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec

30mA less than 0.1 sec
30mA less than 0.1 sec

Summary of Contents for I19

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Page 2: ......

Page 3: ...ch 4 5 4 6 4 7 Silent 4 8 4 9 4 10 4 11 Main board 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Parameter list and breakdown table Cable specific...

Page 4: ...mming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Dur...

Page 5: ...The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Applia...

Page 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Page 7: ...oise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight Nominal Heating Capacity kW Btu h kW Btu h kW kW A A W R...

Page 8: ...antity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net...

Page 9: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Modles Oasis I9 Oasis I12 unit mm 2 SPECIFICATION 6 545 956 1000 398...

Page 10: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Models Oasis I19 unit mm 2 SPECIFICATION 7 Water inlet 40 Water outlet 40 96 790 490 862 466 1115 1160 467...

Page 11: ...teps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary t...

Page 12: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Page 13: ...o the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand a...

Page 14: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Page 15: ...ed to enter and exit the mute mode with one click 4 2 Key and icon function instruction Key symbols It is used to switch the unit mode temperature setting and parameter setting It is used to carry out...

Page 16: ...the unit It will display when compressor is started It will display when water pump is started It will display when fan is started When the timing mute function is started it keeps bright for a long...

Page 17: ...shut down the wire controller will display as follows Operations are the same as under ON OFF main interface 4 4 Mode switch Under the main interface Short press to switch the unit among heating cooli...

Page 18: ...When the unit is under the defrosting state the defrosting symbol is on with the display interface as follows Notes 1 After completing the defrosting the unit will be automatically switched to the hea...

Page 19: ...erating steps the changes will not be saved and return to the main interface Under the clock setting interface Long press for 2 s to enter into the system times setting interface Short press Press or...

Page 20: ...interface Notes 1 Under the Timer ON OFF setting interface if there is no operation for 20 s the system will automatically memorize user s settings and return to the main interface 2 Under the Timer O...

Page 21: ...p long press of for 2 s Short press or Short press for entering the hour digit setting of timing on silent Short press or Short press for confirming the timing on silent and turn to the setting of tim...

Page 22: ...nd the screen will be lighten after other operations conducted 2 Under the OFF interface locking operation is available and the operation method is the same as locking screen under the ON interface 2...

Page 23: ...sor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and cold circuit check and replace this temp sensor Check whether fan motor is broken or locked...

Page 24: ...nt Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Check the communication connection Check the PFC switch tube short circuit or not Ch...

Page 25: ...n Instruction 10 2 Parameter list Meaning 28 28 27 Remarks Adjustable Adjustable Adjustable Default Refrigeration target temperature set point Heating the target temperature set point Automatic target...

Page 26: ...23 Controller interface diagram and definition 4 11 Main board Oasis I9 I12 4 Use and Operation Instruction 1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 1 2 ACN1 ACL1...

Page 27: ...1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 Controller interface diagram and definition 4 11 Main board Oasis I19 24 4 Use and Operation Instruction 1 2...

Page 28: ...put Water output temperature input System fan coil temperature input Ambient temperature input System Exhaust temperature input Earth wire Earth wire System suction temperature input Water input tempe...

Page 29: ...Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shall b...

Page 30: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Page 31: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Page 32: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Page 33: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Page 34: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Page 35: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Page 36: ...33 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I9 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 37: ...e switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat ex...

Page 38: ...35 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I12 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 39: ...re switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat e...

Page 40: ...6 APPENDIX 6 3 Explosive view of the unit 37 Moddel Oasis I19 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Page 41: ...Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat exchanger...

Page 42: ...Note...

Page 43: ......

Page 44: ...Code 20190508 0001...

Reviews: