- 9 -

POWER LINE

terminals 1-2

Connect to a 230 Vac ± 10%, 50 Hz, single-phase power source.
Connect NEUTRAL to terminal 1. Connect POSITIVE to terminal 2.
Connect EARTH to the internal earth terminal on the body of the unit.
We advise the installation of a 10A thermal cut-out switch upstream.
The controller is protected by a high-speed 160 mA fuse (F1-TRS).

MOTOR

connector J4

Supplied already wired and tested together with the 10 

μ

F 450Vac condenser.

Protection against overcurrents by means of quick 4 A fuse (F3 - ENG).
Regulation of working time (WORK TRIMMER) to protect the motor in the event of travel stop fault.
Dip-switch 7 makes it possible to invert the direction, which facilitates mounting the motor in any position.

TRAVEL STOPS

connector J5

Supplied already fitted and tested (FCA on terminals 20-22 ; FCC on terminals 21-22 ).
Check: with gate open, FCA LED off and FCC LED on; with gate closed, FCC LED off and FCA LED on.

PUSHBUTTON PANEL

terminals 7-8-9-10; 7-8-43

Accessories.
The PT3/S pushbutton panel (Start, Stop, Indicator light) or the PT2/S pedestrian panel (Start,Stop) is used.
Connect the Start button to terminals 8-9 (N.O. contact) for complete opening/closing or to terminals 8-43
(N.O. contact) for partial opening. Check that the related command lights up the RUN or PAR LED, respectively.
Connect the Stop button to terminals 7-8 (N.O. contact) and the 24 Vac- 3W light to terminals 8-10.
The function indicator light flashes rapidly when the gate is closing; it remains off when the gate is closed.
The light flashes slowly when the gate is opening, and when the gate is open, the light is on.
A similar indication is given by the LGT LED situated on the controller.

N.B.:

If the Stop button is not connected, the controller is not enabled. In this case, short circuit
terminals 7-8 and check that the STP LED is normally lit.

KEYED SWITCH UNIT

terminals 7-8-9-43

Accessory: keyed switch unit model SCZ.
Connect the N.O. contact of the unit to terminals 8-9 for complete opening or to terminals 8-43 for pedestrian opening.
Connect the N.C. contact to terminals 7-8 to obtain the Stop function.

MAGNETIC KEY READER

terminals 8-9-43

Accessory: reader model SCK.
Use the related N.O. contact to obtain the Start function (terminals 8-9) or pedestrian Start (terminals 8-43)
If only the reader is used, and not the pushbutton panel, short circuit terminals 7-8.

MAGNETIC DETECTOR

terminals 7-8; 8-9; 18-19

Accessory: magnetic detector model RM416-8 can be used as a Start, Stop or security control.
To use as a Start control, connect N.O. to terminals 9 and 8.
To use as a Stop control, connect N.C. to terminals 8 and 7.
To use as a Security control, connect N.C. to terminals 18 and 19.
Check: the presence of a metallic body on the coil turn should cause the RUN LED to light up and the
STP or LUX LED to go off.

PHOTOCELL

terminals   14-15-18-19

Accessory.
Connect terminals 1-2 of transmitter TX to terminals 14-15 of the controller.
Connect terminals 1-2 of receiver RX (24 Vac) to terminals 14-15 of the controller.
Terminals 14-15 supply a 24Vac utility protected by a 500 mA fuse (F4-24V).
Connect terminals 4-5 of the receiver to terminals 18-19 of the controller.
Check: with photocell interrupted, LUX LED is off. Select the programme desired using dip-switch 5.

F

LASHER

terminals  11-12

Accessory: flasher model SLR shows

 that the system is operating.

Connect terminals 11 and 12, following the numbering.
When dip-switch 4 in positioned to ON, the flasher begins operating 2.5 sec. before each phase of movement.
The output is protected by a special 250 mA fuse (F2-SLR) : only use 230Vac lamps of max. 40W.

CONNECTION INSTRUCTIONS

Summary of Contents for ASX03I

Page 1: ...NUALE D INSTALLAZIONE ED USO ELECTRONIC EQUIPMENT pag 7 INSTALLATION AND OPERATION MANUAL APPAREILLAGE ELECTRONIQUE pag 11 MMANUEL D INSTALLATION ET D UTILISATION ELEKTRONIK pag 15 INSTALLATIONS UND B...

Page 2: ......

Page 3: ...scita luce cortesia 200W Fusibile uscita lampeggiatore 250 mA Temperatura di funzionamento 20 70 AVVERTENZE Installare l unit e i vari dispositivi secondo le normative di sicurezza vigenti Allacciarsi...

Page 4: ...ONNETTORE REVERSER TRIMMERS CONNETTORE RADIO TASTO DI RESET F1 TRS 160mA F2 SLR 250mA F3 ENG 4A F4 24V 500mA LED LGT TRASFORMATORE F3 F1 F2 F4 DIP SW DI PROGRAMMAZIONE MORSETTI ESTRAIBILI 1 2 LINEA MO...

Page 5: ...chiave mod SCZ Collegare il contatto NA del selettore ai morsetti 8 9 per l apertura totale oppure all 8 43 per l apertura pedonale Collegare il contatto NC ai morsetti 7 8 per ottenere la funzione St...

Page 6: ...no lampeggiare tutti i leds di Status salvo quelli relativi ai contatti NC che resteranno accesi Si dovr ascoltare l inserimento in sequenza dei 4 rel e l accensione del led LGT Verifica Agendo sui tr...

Page 7: ...he various devices according to the current safety standards Connect up with the 230 V AC mains only down line from a differential or thermal cut out switch Always separate the power cables from the c...

Page 8: ...ERSER CONNECTOR TRIMMERS RADIO CONNECTOR RESET BUTTON F1 TRS 160mA F2 SLR 250mA F3 ENG 4A F4 24V 500mA LGT LED TRANSFORMER F3 F1 F2 F4 PROGRAMMING DIP SWITCH REMOVABLE TERMINALS DIP FUNCTION PROGRAMS...

Page 9: ...ected the controller is not enabled In this case short circuit terminals 7 8 and check that the STP LED is normally lit KEYED SWITCH UNIT terminals 7 8 9 43 Accessory keyed switch unit model SCZ Conne...

Page 10: ...the controller microprocessor and related inputs outputs Procedure Set dip switches 1 and 2 to OFF and press the RESET key Check All the Status LEDs should flash except for those related to the N C co...

Page 11: ...parer toujours les c bles de puissance des c bles de commande et de s curit poussoirs cellules photo lectriques etc en utilisant si possible des guaines s par es Contr ler les connexions lectriques a...

Page 12: ...PE FUSIBLES GROUPE RELAIS CONNECTEUR REVERSER TRIMMERS CONNECTEUR RADIO TOUCHE RESET F1 TRS 160mA F2 SLR 250mA F3 ENG 4A F4 24V 500mA LED LGT TRANSFORMATEUR F3 F1 F2 F4 MICRO INTERR DE PROGRAMM BORNES...

Page 13: ...7 8 et v rifier que le LED STP soit normalement allum SELECTEUR A CLE bornes 7 8 9 43 Accessoire s lecteur cl mod SCZ Connecter le contact NO du s lecteur aux bornes 8 9 pour l ouverture totale ou bie...

Page 14: ...dure Mettre les 1 et 2 sur OFF et appuyer sur la touche RESET Contr le Tous les LED de contr le doivent clignoter except ceux correspondants aux contacts NF qui restent allum s Ecouter l enclenchemen...

Page 15: ...Anschl sse berp ft werden falsche Anschl sse k nnten Folgesch den des Ger tes bewirken HINWEISE TECHNISCHE EIGENSCHAFTEN Stromversorgung 230Vac 10 50Hz Max Leistungsaufnahme 500 W Maximallast Zubeh r...

Page 16: ...ANN ANWESEND ON OFF HALBAUTOMATISCH ON ON AUTOMATISCH 3 FOLGE DER START BEDIENUNGEN OFF FFNEN SCHLIESSEN NUR BEI FCA STOPPUNG UND FFNEN BEIM SCHLIESSEN MEHRFAMILIENH USER ON FFNEN STOP SCHLIESSEN STOP...

Page 17: ...lter Mod SCZ Den Schlie erkontakt des W hlschalters zur vollst ndigen ffnung an die Klemmen 8 9 anschlie en oder zur Fu g nger ffnung an die Klemmen 8 43 Den ffnerkontakt f r die Stop Funktion an die...

Page 18: ...die RESET Taste dr cken Kontrolle Alle Zustandsleds m ssen blinken mit Ausnahme der ffnerkontaktleds welche an bleiben Die Sequenzeinschaltung der 4 Relais mu abgeh rt und das Aufleuchten der LGT Led...

Page 19: ...r a la red 230 Vca s lo despu s de un interruptor t rmico o diferencial Separar siempre los cables de potencia de los cables de mando y seguridad pulsantes fotoc lulas etc utilizando si fuera posible...

Page 20: ...NVERSOR TRIMMERS CONNECTOR RADIO RECEPTOR TECLA DE RESET F1 TRS 160mA F2 SLR 250mA F3 ENG 4A F4 24V 500mA LED LGT TRANSFORMADOR F3 F1 F2 F4 DIP SW DE PROGRAMA BORNES EXTRAIBLES 1 2 LINEA DE ALIMENTACI...

Page 21: ...ed STP est normalmente encendido SELECTOR DE LLAVE bornes 7 8 9 43 Accesorio selector de llave mod SCZ Conectar el contacto NA del selector con los bornes 8 9 para la abertura total o con el 8 43 para...

Page 22: ...inserto en el respectivo conector J2 El ciclo peatonal est compuesto por una abertura de 8 de duraci n y un tiempo de pausa fijo de 10 al final del cual se cierra autom ticamente El programa es aut no...

Page 23: ......

Page 24: ...FERENCIAS RIVENDITORE RESALER REVENDEUR WIEDERVERK UFER REVENDEDOR INSTALLATORE INSTALLER INSTALLATEUR INSTALLATEUR INSTALATOR UTENTE USER UTILISATEUR VERBRAUCHER USUARIO O O srl Via Europa 2 42015 CO...

Reviews: