Installation instruction for connection kit nVent RAYCHEM CCON20-100-PI-...
For exclusive use with PI series heating cables permitted by nVent.
SEV 05 ATEX 0147 U
II 2GD EEx e II IP66
TC RU C-BE.ИМ43.В.01854
Ex e IIC Gb U Ex tb IIIC Db U
Ta -55°C…+40°C
ООО “ТехИмпорт”
This kit contains an adaptor ref. CCON20-.. separately approved under
SEV 05 ATEX 0140
Ambient temperature: –55°C to +40°C
Storage and transportation
- Store and transport product in a clean, dry place
- Store and transport at temperatures between –55°C and +40°C
- Protect product from moisture, direct sunlight and mechanical damage
The metal part of the gland outside the junction box does not need to be
grounded if WAGO CAGE CLAMP terminals (series 283, 284 or 285) are used
and the maximum strip length of the cables are respected.
nVent requires the use of a 30 mA residual current device to provide maximum
safety and protection from fire. Where design results in a higher leakage
current, a maximum 300 mA residual current device may be used. All safety
aspects need to be proven.
WARNING: To prevent electrical shock, short circuit or arcing, this product
must be installed correctly and water ingress must be avoided before and during
the installation.Recommended maintenance is a visual inspection at least every
3 years. Only replace broken parts by appropriate original spare parts.
Before installing this product, read these instructions completely and
thoroughly follow all steps!
PI series heating cables can be directly terminated into the junction box
(no cold lead required). The following conditions must be respected to comply
with approval requirements:
Table 1
Junction box used as power box (min. box size: 160 x 160 x 90 mm)
Nom. resistance PI series heating cable
≥ 10 Ω/km
7 Ω/km
Max. power output
15 W/m
15 W/m
Max. heating cable length in box
40 cm
40 cm
Min. terminal size *
10 mm
2
16 mm
2
Power cable selection
Operating current
Minimum power cable size
up to 10 A
2.5 mm
2
up to 15 A
4 mm
2
up to 25 A
6 mm
2
up to 45 A
10 mm
2
Junction box used as splice box (min. box size: 160 x 160 x 90 mm)
Nom. resistance PI series heating cable
≥ 10 Ω/km
7 Ω/km
Max. power output
15 W/m
15 W/m
Max. heating cable length in box
66 cm
66 cm
Min. terminal size *
10 mm
2
16 mm
2
*Terminal types:
10 mm
2
WAGO 284 series
16 mm
2
WAGO 283 series
Summary of Contents for Raychem CCON20-100-PI Series
Page 2: ...10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 0 ...
Page 3: ...nVent com 3 A B C PI ...
Page 24: ...24 nVent com 4 6 5 mm CCON20 100 PI A 6 5 9 5 mm CCON20 100 PI B 9 5 13 mm CCON20 100 PI C 2 ...
Page 27: ...nVent com 27 5 ...
Page 37: ...nVent com 37 ...
Page 38: ...38 nVent com ...
Page 39: ...nVent com 39 ...