7.2 Controller
Controller type and controller input values, set point limit
values, functions for manual mode and the presettings of self-
optimization are set here.
ConF
->
Cntr
->
Parameters
Value /
Selection
Description
Controller type
CtyP
1
2
3
4
2-state controller
3-state controller
Modulating controller
Continuous controller
Control
direction
CACt
0
1
Direct
)
2
(
)
1
(
Inverse
(1) = Inverse:
Output value Y of the controller is > 0,
if process value x is smaller than set point
value w (e.g. heating).
(2) = Direct:
Output value Y of the controller is > 0,
if process value x is higher than set point
value w (e.g. cooling).
Output value,
manual mode
HAnd
-100 …
+101
Defines the output value after switching
to manual mode.
101 = last output value
For modulating controllers:
0 = Actuator closes
100 = Actuator opens
101 = Actuator stops
Setting in the Setup program
(-> Controller -> Output value,
manual mode)
Output value at
Out of Range
rOut
-100 …
+101
Output value in the event of overrange or
underrange.
101 = last output value
For modulating controllers:
0 = Actuator closes
100 = Actuator opens
101 = Actuator stops
Setting in the Setup program
(-> Controller -> Output value at
Out of Range)