40
|
nVent.com
RTD temperature probe input
Designation,
Connection type
Measuring
range
Measuring
accuracy
1
Ambient temperature
coefficient
Pt100 EN
60751
2 wire
connection
3 wire
connection
-200… +850 °C
≤ 0.4%
≤ 0.1%
50 ppm/K
Pt1000 EN
60751
2 wire
connection
3 wire
connection
-200…+850 °C
≤ 0.2%
≤ 0.1%
50 ppm/ K
KTY11-6
2 wire
connection
-50…+150 °C
≤ 0.25%
50 ppm/ K
Sensor lead resistance: max. 30 Ω per lead with three wire circuit
Measuring current: approx. 250 µA
Lead compensation: Not required for three wire circuit. For a 2-wire
circuit, the lead resistance can be compensated by correcting the
actual value.
1
The accuracy values refer to the maximum measuring range.
Small measuring ranges lead to reduced linearisation accuracy.
Standard signals input
Measuring range
Measuring
accuracy
1
Ambient temperature coefficient
Voltage 0(2)—10 V
Input resistance R
E
> 100 kΩ
≤ 0.1%
100 ppm/K
Current 0(4)—
20 mA
Voltage drop ≤
2.2 V
≤ 0.1%
100 ppm/ K
1
The accuracy values refer to the maximum measuring range. Small measuring
ranges lead to reduced linearisation accuracy.