background image

INSTALLATION INSTRUCTIONS

READ & SAVE THESE INSTRUCTIONS!

®

IMPORTANT SAFETY INSTRUCTIONS

WARNING: TO REDUCE THE RISK OF FIRE. ELECTRIC

SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:

A. Use this unit only in the manner intended by the manufacturer.

If you have questions, contact the manufacturer.

B. Before servicing or cleaning unit, switch power off at service

panel and lock service panel to prevent power from being
switched on accidentally.
When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to
the service panel.

CAUTION:

For general ventilating use only. Do not use to exhaust

hazardous or explosive materials and vapors.

INSTALLATION INSTRUCTIONS

WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC

SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:

A. Installation work and electrical wiring must be done by

qualified person(s) in accordance with all applicable codes and
standards, including fire-rated construction.

B. Sufficient air is needed for proper combustion and exhausting

of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer's guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code
authorities.

C. When cutting or drilling into wall or ceiling, do not damage

electrical wiring and other hidden utilities.

D. Ducted fans must always be vented to the outdoors.
E. If this unit is to be installed over a tub or shower, it must be

marked as appropriate for the application.

F. NEVER place a switch where it can be reached from a tub or

shower.

WARNING:

To reduce the risk of fire or electric shock, do not

use this fan with any solid-state speed control.

Not for use in kitchens.

Suitable for use over tub or shower when installed in a GFI 
(or GFCI) Protected Branch Circuit.

The exhaust fan consists of the housing, power unit/blower
assembly (motor, wheel, mounting plate,) grille and duct collar.

• Do not install in a ceiling insulated to a value greater than R-40.

Bathroom 
Exhaust Fan

MODEL: 8814R

SUITABLE FOR USE OVER TUB OR SHOWER ENCLOSURE 
WHEN INSTALLED IN A GFCI PROTECTED BRANCH CIRCUIT.

FOR BEST RESULTS

When installing the exhaust fan in a new construction site,

install housing during the rough-in construction of the building.
The blower unit and grille should be installed after the finished
ceiling is in place.

To install the exhaust fan in an existing finished building

requires an accessible area (attic or crawl space) above the
planned location.

PLANNING DUCTWORK AND WIRING

DUCTWORK

1. Use 4" round duct.
2. Plan to run duct from discharge opening of fan to the outside.

For best fan performance, make duct run as short as possible.

3. Use optional NuTone ducting accessories as needed. Refer to

your NuTone catalog for a complete listing of available
accessories.

WIRING

Plan to run 120vAC house wiring (with ground) from power

source, through a standard wall switch to junction box in fan
housing.

FIGURE 1

DUCT
COLLAR

HOUSING

SLOTS

POWER UNIT/
BLOWER
ASSEMBLY

TABS

GRILLE

Summary of Contents for 8814R

Page 1: ...r hidden utilities D Ducted fans must always be vented to the outdoors E If this unit is to be installed over a tub or shower it must be marked as appropriate for the application F NEVER place a switc...

Page 2: ...he planned finished ceiling Extend the hanger bars to the joists 3 Use screws or nails not provided to secure hanger bars to ceiling joists INSTALLING THE DUCTWORK 1 Refer to Figure 2 Place duct colla...

Page 3: ...or b any products or parts which have been subject to misuse negligence accident improper maintenance or repair other than by NuTone faulty installation or installation contrary to recommended instal...

Page 4: ...D Les ventilateurs avec gaine doivent toujours avoir une une vacuation ext rieure E Si cette unit doit tre install au dessus d une baignoire ou d une douche une stipulation sp cifique pour cette util...

Page 5: ...ontage plac es sur le bord inf rieur du bo tier Clouer une barre aux solives 3 Coulisser le bo tier l endroit voulu entre les solives et clouer alors la seconde barre aux solives REMARQUE Le bo tier n...

Page 6: ...l entretien et le service courants ni b les produits et les pi ces ayant fait l objet d un usage abusif de n gligence d un accident d un entretien ou d une r paration non appropri e par du personnel...

Page 7: ...da como apropiada para la aplicaci n F No coloque NUNCA un interruptor donde pueda ser alcanzado desde la ba era o ducha ADVERTENCIA Para reducir el riesgo de incendio o choque el ctrico no utilice es...

Page 8: ...taje en las ranuras provistas en el bastidor 2 Posicione el bastidor del ventilador entre las vigas de manera que la parte inferior del bastidor est al mismo nivel con el techo terminado planificado E...

Page 9: ...S O A LOS TUBOS FLUORESCENTES FILTROS DUCTOS TAPAS DE TECHO TAPAS DE PARED Y OTROS ACCESORIOS PARA CANALIZACI N Esta garant a no cubre a Mantenimiento y servicios normales b Productos o partes sujetos...

Page 10: ...86933 000 5 51919 BLOWER WHEEL 51919 000 6 63007 PUSH NUT 63007 000 7 30652 DUCT ADAPTER ASSEMBLY 30652 000 8 44208 GRILLE SPRING ASSEMBLY 44208 000 9 10034 RECEPTACLE 10034 000 EFFECTIVE DATE PRODUC...

Reviews: