background image

3

nuaire.co.uk 

029 2085 8400

13. 03. 19. Document Number  671188

Installation and Maintenance

Ecosmart Boxer Air Handling Units

3.0 INSTALLATION

Installation must be carried out by competent personnel in 
accordance with the appropriate authority and conforming to all 
statutory and governing regulations e.g. IEE, CIBSE etc.

3.1 Erection

Unit sizes 1 and 2 are generally single section units and require no 
assembly.

Unit sizes 3 to 7 are multi-section units supplied on a base frame. The 
units and base frame will require bolting together using matched drilled 
flanges and the nuts and bolts provided. In addition fish-plates must be 
used to join two base frames together (Figure 5).

Note: It is the assembler’s responsibility to seal all modular facing 
joints.

3.2.2 Electrical

On sizes 3 to 7 the various modular sections are delivered separately for 
assembly on site.

Ensure that all inter-connecting wiring looms are connected 
between the adjoining modules - refer to the appropriate wiring 
diagram in section 5.

When selecting the unit position, ensure adequate access for 
connection of external services, commissioning, future inspection and 
maintenance and the removal of component parts.

3.2.3 Indoor Installation

The standard fan is suitable for installation indoors only, away from 
heat sources, steam generation or water spray. Site the fan on a secure 
and level surface, using the base frame provided, suspend on a platform 
or support rails, alternatively hang using drop rods.

3.2.4 External Installation

Where an external installation is 
required, install on a secure and 
level surface, use the base frame 
and the weather roof tailored 
for each system. Connect 
ducting, inlet or extract cowls 
as appropriate.

3.2.5 Wet Pipe Connections

3.2 Assembly of Equipment

3.2.1 Mechanical

Ensure all components and sections are available to complete the work. 
The flanges of facing sections must be offered one to the other, and 
secured via the studs and nuts provided. Access to each securing point 
is by removal of the access doors on each section. Each joint must be 
appropriately sealed to ensure weathering and to prevent air leakage.

Where cooling coils and heat exchangers are in use condensate 
drainage points are provided. It is the installers’ responsibility to 
ensure connection to the appropriate trap and drainage.

On sizes 1 and 2, where motorised dampers are coupled to a system, 
it will be necessary to remove the spigot section inlet/discharge to 
fix the damper into position. Where ancillaries such as silencers, bag 
filters, frost heaters etc. are to be fitted, each additional component is 
supplied with a fixing kit (Figure 6).

NB: The flow valve is not factory set and should be adjusted by the 
commissioning engineer.

Slot fishplate into ends
of base frames and bolt 
together.

Unit base frame.

Use nuts and studs 
to join flanges of 
facing sections.

Figure 5.  

Figure 7.  Weather Roof

Figure 6. Fixing kit in use on  
sizes 1 and 2. One to be used  
at top and bottom of sections. 

Figure 8. Typical wet coil pipe termination arrangement.

Unit Model

Frost Coils

CHW Coils

LPHW Coils

ESBHS1

0.75" BSP

1" BSP

1.25" BSP

ESBHS2

0.75" BSP

1.25" BSP

1.25" BSP

ESBHS3

1" BSP

1.25" BSP

1.25" BSP

ESBHS4

1" BSP

1.25" BSP

1.5" BSP

ESBHS5

1.25" BSP

1.5" BSP

2" BSP

ESBHS6

1.25" BSP

2" BSP

2" BSP

ESBHS7

1.5" BSP

2" BSP

2" BSP

Summary of Contents for ESBH Series

Page 1: ...t Terminals Weathering Roof Sensors User controls For systems which include supply fans with heating and or cooling coils other than where the BMS has control the appropriate user control is required...

Page 2: ...etised Forklift Slings via spreaders fitted to unit with base frame Figure 2 Figure 3 Figure 4 2 0 HANDLING Upon receipt of the equipment an inspection should be made and before commencement of liftin...

Page 3: ...equired install on a secure and level surface use the base frame and the weather roof tailored for each system Connect ducting inlet or extract cowls as appropriate 3 2 5 Wet Pipe Connections 3 2 Asse...

Page 4: ...erse effect on lighting etc There are no inrush starting currents quoted because the Ecosmart control incorporates a soft starting speed control feature The inverters are pre set to match the fan heat...

Page 5: ...itted DX2 coil Signal for if fitted 25 30 2 5 Set air off of LPHW coil temperature 0V 0 10V BMS signal Connections to Damper N L SL DP CL N RET Remove this link wire if NET connections for ECOSMART de...

Page 6: ...n 2 Heating Cooling Fault Frost Tx Rx Ecosmart signal Heat demand Run signal Fault signal DAMPER FAULT RUN HEAT DEMAND L3 L2 L1 N E 400V 50Hz 3ph N mains supply for fan 5 6 3 1 4 2 U V W E L1 L2 L3 U...

Page 7: ...1 15 13 14 12 9 7 5 8 6 10 11 15 12 14 13 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost alarm signal DX1 coil Signal for if fitted Signal for DX2 coil if fitted 25 3 0 25 Set air...

Page 8: ...15 13 14 12 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost signal alarm DX1 coil Signal for if fitted DX2 coil Signal for if fitted Connect to inlet sensor after unit is assemble...

Page 9: ...e as Data cable installation Keep the cable run as short as possible and less than 50 metres 4 1 9 BMS Input Signals The BMS connection is made with a plug in connector via the socket Figure 22 To ens...

Page 10: ...hen a fault is present on unit Frost Not applicable see note Tx LED on when the controller is transmitting data Rx LED on when the controller is receiving data Note that the control panel is common to...

Page 11: ...lt Tension Size 7 All belt drive units incorporate belt tensioning devices To adjust the belt tension slacken the pinch bolt on the sides of the motor plate Turn the adjusting bolt clockwise to tighte...

Page 12: ...s of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orie...

Reviews: