background image

12

nuaire.co.uk 

029 2085 8400

13. 03. 19. Document Number  671188

DECLARATION OF INCORPORATION AND INFORMATION FOR SAFE INSTALLATION,  
OPERATION AND MAINTENANCE

INFORMATION FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE
OF NUAIRE VENTILATION EQUIPMENT

We declare that the machinery named below is intended to be assembled with 
other components to constitute a system of machinery. All parts except for 
moving parts requiring the correct installation of safety guards comply with the 
essential requirements of the Machinery Directive. The machinery shall not be 
put into service until the system has been declared to be in conformity with the 
provisions of the EC Machinery Directive.

Designation of machinery:  

 

ECOSMART BOXER FANS

Machinery Types:    

 

ESBS, ESBEX

Relevant EC Council Directives:  

2006/42/EC (Machinery Directive)

Applied  Harmonised  Standards:  

BS EN ISO 12100-1, BS EN ISO 12100-2, 

 

 

 

 

EN294, EN60204-1, BS EN ISO 9001

Applied National Standards: 

 

BS848 Parts One, Two and Five

Signature of manufacture representatives:

Name: 

  Position: 

  Date: 

1)C. Biggs   

 

Technical Director 

 

20. 07. 07 

 
2)A. Jones   

 

Manufacturing Director   

20. 07. 07 

 

To comply with EC Council Directives 2006/42/EC Machinery Directive and 2014/30/EU (EMC).
To be read in conjunction with the relevant product documentation (see 2.1)

1.0  

GENERAL

1.1  

The equipment referred to in this 

Declaration of Incorporation

 is supplied by Nuaire to

 

be assembled into a ventilation system which may or may not include additional

 components.
 

The entire system must be considered for safety purposes and it is the responsibility of

 

the installer to ensure that all of the equipment is installed in compliance with the

 

manufacturers recommendations and with due regard to current legislation and codes

 

of practice.

2.0  

INFORMATION SUPPLIED WITH THE EQUIPMENT

2.1  

Each item of equipment is supplied with a set of documentation which provides the

 

information required for the safe installation and maintenance of the equipment.

 

This may be in the form of a Data sheet and/or Installation and Maintenance instruction.

2.2  

Each unit has a rating plate attached to its outer casing. The rating plate provides

 

essential data relating to the equipment such as serial number, unit code and electrical

 

data. Any further data that may be required will be found in the documentation.

 

If any item is unclear or more information is required, contact Nuaire.

2.3 

Where warning labels or notices are attached to the unit the instructions given must be

 

adhered to.

3.0  

TRANSPORTATION, HANDLING AND STORAGE

3.1  

Care must be taken at all times to prevent damage to the equipment. Note that shock

 

to the unit may result in the balance of the impeller being affected.

3.2 

 When handling the equipment, care should be taken with corners and edges and that

 

the weight distribution within the unit is considered. Lifting gear such as slings or ropes

 

must be arranged so as not to bear on the casing.

3.3  

Equipment stored on site prior to installation should be protected from the weather and

 

steps taken to prevent ingress of contaminants.

4.0  

OPERATIONAL LIMITS

4.1  

It is important that the specified operational limits for the equipment are adhered to

 

e.g. operational air temperature, air borne contaminants and unit orientation.

4.2  

Where installation accessories are supplied with the specified equipment eg.

 

wall mounting brackets. They are to be used to support the equipment only.

 

Other system components must have separate provision for support.

4.3  

Flanges and connection spigots are provided for the purpose of joining to duct work

 

systems. They must not be used to support the ductwork.

4.4  

Local Environment - Humidity.

 Ambient humidity (the humidity at the unit’s installed

 

location) shall be within the range: 10 to 95% (for controls, non-condensing).

 

Air humidity (the humidity of the air passing through the unit) shall be within the

 

range: 10 to 95% (for controls, non-condensing).

5.0  

INSTALLATION REQUIREMENTS

 

In addition to the particular requirements given for the individual product, the following

 

general requirements should be noted.

5.1 

 Where access to any part of equipment which 

moves

, or can become 

electrically live

 are

 

not prevented by the equipment panels or by fixed installation detail (e.g. ducting), then

 

guarding to the appropriate standard must be fitted.

5.2 

 The electrical installation of the equipment must comply with the requirements of the

 

relevant local electrical safety regulations.

5.3 

 For EMC all control and sensor cables should not be placed within 50mm or on the same

 

metal cable tray as 230V switched live, lighting or power cables and any cables not

 

intended for use with this product.

6.0 

 COMMISSIONING REQUIREMENTS

6.1 

 General pre-commissioning checks relevant to safe operation consist of the following:

 

Ensure that no foreign bodies are present within the fan or casing.

 

Check electrical safety. e.g. Insulation and earthing.

 

Check guarding of system.

 

Check operation of Isolators/Controls.

 

Check fastenings for security.

6.2 

 Other commissioning requirements are given in the relevant product documentation.

7.0 

 OPERATIONAL REQUIREMENTS

7.1  

Equipment access panels must be in place at all times during operation of the unit, and 

 

must be secured with the original fastenings.

7.2  

If failure of the equipment occurs or is suspected then it should be taken out of service

 

until a competent person can effect repair or examination. (Note that certain ranges of

 

equipment are designed to detect and compensate for fan failure).

8.0  

MAINTENANCE REQUIREMENTS

8.1  

Specific maintenance requirements are given in the relevant product documentation.

8.2  

It is important that the correct tools are used for the various tasks required.

8.3  

If the access panels are to be removed for any reason the electrical supply to the unit

 

must be isolated.

8.4  

A minimum period of two minutes should be allowed after electrical disconnection before

 

access panels are removed. This will allow the impeller to come to rest.

 

NB: Care should still be taken however since airflow generated at some other point

 

in the system can cause the impeller to “windmill” even when power is not present.

8.5  

Care should be taken when removing and storing access panels in windy conditions.

Note: All standards used were current and valid at the date of signature.

Summary of Contents for ESBH Series

Page 1: ...t Terminals Weathering Roof Sensors User controls For systems which include supply fans with heating and or cooling coils other than where the BMS has control the appropriate user control is required...

Page 2: ...etised Forklift Slings via spreaders fitted to unit with base frame Figure 2 Figure 3 Figure 4 2 0 HANDLING Upon receipt of the equipment an inspection should be made and before commencement of liftin...

Page 3: ...equired install on a secure and level surface use the base frame and the weather roof tailored for each system Connect ducting inlet or extract cowls as appropriate 3 2 5 Wet Pipe Connections 3 2 Asse...

Page 4: ...erse effect on lighting etc There are no inrush starting currents quoted because the Ecosmart control incorporates a soft starting speed control feature The inverters are pre set to match the fan heat...

Page 5: ...itted DX2 coil Signal for if fitted 25 30 2 5 Set air off of LPHW coil temperature 0V 0 10V BMS signal Connections to Damper N L SL DP CL N RET Remove this link wire if NET connections for ECOSMART de...

Page 6: ...n 2 Heating Cooling Fault Frost Tx Rx Ecosmart signal Heat demand Run signal Fault signal DAMPER FAULT RUN HEAT DEMAND L3 L2 L1 N E 400V 50Hz 3ph N mains supply for fan 5 6 3 1 4 2 U V W E L1 L2 L3 U...

Page 7: ...1 15 13 14 12 9 7 5 8 6 10 11 15 12 14 13 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost alarm signal DX1 coil Signal for if fitted Signal for DX2 coil if fitted 25 3 0 25 Set air...

Page 8: ...15 13 14 12 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost signal alarm DX1 coil Signal for if fitted DX2 coil Signal for if fitted Connect to inlet sensor after unit is assemble...

Page 9: ...e as Data cable installation Keep the cable run as short as possible and less than 50 metres 4 1 9 BMS Input Signals The BMS connection is made with a plug in connector via the socket Figure 22 To ens...

Page 10: ...hen a fault is present on unit Frost Not applicable see note Tx LED on when the controller is transmitting data Rx LED on when the controller is receiving data Note that the control panel is common to...

Page 11: ...lt Tension Size 7 All belt drive units incorporate belt tensioning devices To adjust the belt tension slacken the pinch bolt on the sides of the motor plate Turn the adjusting bolt clockwise to tighte...

Page 12: ...s of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orie...

Reviews: