Installation Manual
4.0 ELECTRICAL INSTALLATION
The electrical connection of the unit must be carried out by a
qualified electrician.
4.1 Electrical Information
Voltage:
230V 1ph 50Hz
Consumption:
2W(min) 24W(max)
Fuse Size:
3A
4.2 Wiring
This unit MUST be earthed.
The three core cable from the mains power supply should be
connected to a fixed wiring installation, via a fused isolator, in
accordance with current IEE wiring regulations.
Isolate from power supply before removing any covers. During
installation / maintenance ensure all covers are fitted before
switching on the mains supply.
Before the unit is operational, additional wiring is necessary:
•
A 230V single phase supply is required to be connected to the
circuit board within the unit, via the electrical gland (supplied) on
the side of the Drimaster365.
•
A boost switch (supplied) is to be connected to the circuit board
with two core cable (supplied), via the grommet at the front of the
unit.
•
The remote sensor (supplied) is to be connected to the circuit
board with two core cable (supplied), via the grommet at the front
of the unit.
10
Fan Unit PCB
sensor
To remote
switch
To Boost
To be connected
to remote sensor
To be connected
to sensor
to Boost switch
Not used
Not used
Already connected
to blower
Already
connected
Already
Already connected
connected
Supply
230V A.C.
to 230V mains
N
To be connected
N
L
D
AMPER
Sensor
N
ormal
Boo
st
swit
ch
Summer
The
rmi
stor
Rem
ote
W
in
ter
swit
ch
Ju
m
per
11
Fan Unit Cables & Speed Indicator
RESET
Speed 1
Cable to Boost
Six speed
Cable to house
Switch supplied.
Speed 6
sensor supplied.
indicator lights.
5.0 CONTROLS
5.1 Fan Speed Adjustment
The unit has 6 air volume (speed) settings. The setting switch is located
on the rear of the fan case. 6 speed indicator lights on the rear panel
of the fan unit include LED’s that, when illuminated, indicate the
corresponding air volume for the unit.
For example, a one bedroom, one person bungalow recommended
setting would be speed 1. A five bedroom, seven person detached house
recommended setting would be speed 6. The installer would advise
this on install.
On initial set up when power is connected the first 3 LED’s will flash
randomly for approximately 2 minutes and will then set at its default
factory setting (speed 2). To select another speed setting simply press
the reset button until the required setting is selected.
A boost switch (supplied) is to be connected to the circuit board
within the unit with 2 core cable (supplied). This 2 core cable is to pass
through the unit as shown opposite. The switch is to be located within
the home for the householder to be able to boost the unit if required.
The unit air volume can be manually boosted to maximum speed by
operation of the boost switch. This is to obtain maximum ventilation
from the unit should the householder require it.
5.2 Smoke / Carbon Monoxide Alarm Automatic Shut Down
If the unit is required to switch off in the event of smoke/CO detection,
alarms are available with separate relay bases from companies such as:
Kidde – www.kiddesafetyeurope.co.uk
Aico Ltd – www.aico.co.uk
This is a mandatory requirement for all units installed in a 3 Storey
property.
12
Smoke / Carbon Monoxide Alarm Wiring
POWER
SUPPLY
FAN
UNIT
Mains power Smoke/CO detector
with NO/NC contacts
NC
NO
N
L
N
L
C
230V
Supply
230V
24V
For information only,
refer to manufacturer’s
specific instructions.