3.4 Air Intake & Ducting Connections

Any air intake terminal MUST be installed in accordance with 
appropriate regulation.

As a guide, the BS5440 series of British Standards deals with this 
issue and currently states that an air intake must be at a minimum 
distance of 300mm from a gas boiler balanced flue. Installers are 
advised to be aware of the requirements of this standard when 
installing ‘through the wall’ supply air ducting. Similarly, supply 
and extract air grilles should be at least 300mm apart.

As explained previously the unit is capable of drawing in external air 
from different roof locations via an air inlet spigot (see overleaf).

Air inlet locations are as follows:

Soffit Installation: The soffit through a grille and ducting, supplied 
by others.

Wall Installation: Wall grille and ducting, supplied by others.

The following installation materials, not supplied with the unit, can be 
purchased separately, direct from Nuaire.

Tel: 02920 858500   

E-mail: [email protected]

Kit 

Type

Part No.

Description

DRI365-

SOFITKIT

775229

128mm x 260mm soffit grille

PVC933WH

3m length of 222mm x 90mm flexible PVC ducting for use 
on soffit inlets

FLDI150

5m length of 150mm dia insulated ducting

RDC150

150mm duct connector for connecting 222 x 90 flexible 
duct to 150mm duct

777483

2m length insulated flexible ducting

DT33

Qty 8 dynotie zip ties, used for connecting ducting to 
spigots

DRI365-W

ALLKIT

FLD1150

5m length of 150mm dia. Insulated ducting

777483

2m length insulated flexible ducting.

PVC604WH

Outlet grille

PVC130-6WH

150mm telescopic pipe

DT33

Qty 8 dynotie zip ties, used for connecting ducting to 
spigots

3.4.1 Soffit Installation

 

Typical Soffit Air Inlet & Ducting

Soffit grille (Part No. 775229) fixes over rectangular ducting which 
has been pulled through the rectangular hole (220mm X 80mm) 
cut in soffit and folded flat up against the surface of the soffit.
Note that a minimum soffit width of 130mm is required.

Form end of rectangular 
ducting to fit connector 
and secure using 
dynotie connector.

150mm dia. insulated 
ducting connected to 
unit spigot using 
dynotie connector
(Part No. FLDI150).

220mm x 90mm flexible 
PVC Rectangular ducting 
(Part No. PVC933WH). 
Note: this duct should be 
kept as short as possible.

Circular duct connector
(Part No. RDC150).

3.4.2 Wall Installation

 

Typical Wall Air Inlet & Ducting

150mm dia. insulated ducting

connected to unit spigot using

dynotie connector
(Part No. FLDI150). 

150mm dia. pipe

(Part No. PVC130-6WH).

Insulated duct formed over pipe 

and sealed with dynotie connector.

199 x 215 x 20mm 

white plastic wall grille 

(Part No. PVC604WH).

Summary of Contents for DRI-365

Page 1: ...le guards This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or i...

Page 2: ...ery mode The unit will increase in speed and supply more air to the property The unit can be boosted to obtain maximum ventilation by the operation of a boost switch 3 0 MECHANICAL INSTALLATION Succes...

Page 3: ...d correctly in the central hallway in single storey properties or in the ceiling of the top floor landing on 2 or more storey dwellings The diffuser discharges air evenly in all directions along the u...

Page 4: ...on soffit inlets FLDI150 5m length of 150mm dia insulated ducting RDC150 150mm duct connector for connecting 222 x 90 flexible duct to 150mm duct 777483 2m length insulated flexible ducting DT33 Qty...

Page 5: ...The Remote Temperature Sensor incorporates a clip in fixing bracket which can be removed for easy fitting to a suitable surface Select a suitable location for the sensor e g close to ceiling height in...

Page 6: ...house Switch supplied Speed 6 sensor supplied indicator lights 5 0 CONTROLS 5 1 Fan Speed Adjustment The unit has 6 air volume speed settings The setting switch is located on the rear of the fan case...

Page 7: ...dance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasin...

Page 8: ...8 20 05 21 Document Number 671771 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk DRI 365 Installation Manual NOTES...

Reviews: