DRI-365

Installation Manual

3.3 Fan Unit Installation

3.3.1 Mounting Fan Unit (Standard Configuration)

Connect the two ‘L’ shape fixing brackets to the long sides of the unit 
with the M5 screws (provided) then lower the unit with the “L” shape 
fixing brackets attached to the unit onto the joists. Mark 4 holes 
through the brackets so that the holes will be centrally positioned over 
a joist.

Locate anti-vibration mounts (supplied) above and below each bracket 
fixing  joint hole and, using 4 suitable screws (not provided) and 
washers, fix the unit to the joists. 

Do not over-tighten the fixings.

 

Standard Fan Unit Mounting

Connect fixing brackets
to unit with the 4 M5
screws provided.

Connect 2 ‘L’ shape
fixing brackets and
the AV mounts to
roof joists with
4 suitable screws.

AV mount

Connect fixing brackets 
to the unit with the 
4 M5 screws provided.

Anti-Vibration Mount Installation

Fixing
Bracket 

A.V. 
Mount

3” Woodscrew

Washer

A.V. 
Mount

12mm
Clearance 
Hole

3.3.2 Mounting Fan Unit (Optional Configuration)

Using a similar procedure the two ‘L’ shape fixing brackets can also 
be mounted on the short sides of the DRI-365 unit if an alternative 
mounting position is required.

Optional Fan Unit Mounting

AV mounts.

Connect 2 ‘L’ shape
fixing brackets and 
the 4 AV mounts 
to roof joists with 
4 suitable screws.

Connect fixing brackets 
to ends of unit with 
4 M5 screws provided.

3.2 Ceiling Diffuser Installation

3.2.1 Ceiling Diffuser Location

The diffuser has a unique air throw pattern and it is essential that it is 
located correctly in the central hallway in single storey properties or in 
the ceiling of the top floor landing on 2 or more storey dwellings. The 
diffuser discharges air evenly in all directions along the underside of the 
ceiling.

SMOKE ALARMS -It is also important to ensure that the diffuser is 
NOT placed within 1 metre of a smoke alarm.

Where a floor/room is more than 4.5m tall, the fan unit must be 
fitted with a 3 storey aluminium diffuser and requirements in 
section 5.2 followed. 

If the diffuser cannot be repositioned, two sides of the diffuser must 
be closed off using the air dams supplied to encourage the air through 
the remaining open sides that faces at least 1.5 metres of unobstructed 
area away from the smoke alarm sensor.

Speed Setting

Minimum Distance Between Diffuser & Wall

1

100mm

2

155mm

3

400mm

4

625mm

5

850mm

6

1000mm

3.2.2 Directing Airflow

Air dams should be fitted as needed, to alter the direction of airflow 
required. Two air dams are supplied and will fit on any of the diffuser 
sides to guide airflow away from a smoke detector and/or obstructions. 

Ceiling Vent

Two Air Dams

Diffuser Cap

Airflow

Airflow

Ceiling Diffuser Overview

3.2.3 Mounting Ceiling Diffuser

To install the diffuser, use the tear-out template from the lid of the unit 
packaging and trace the shape onto the ceiling between two convenient 
joists. Once the shape has been cut out, position the ceiling vent by 
aligning the label on the ceiling vent with the narrowest point of the 
ellipse and secure it in place using the 4 screws and plugs provided. 

Finally attach the diffuser cap to the frame using the four built-in press 
on clips provided. 

Fan Unit Overview

150mm dia.

200mm dia.

Flexible Ducting 

Air from loft 

Flexible Ducting 

From outside

Diffuser

air supply 

setting switch is located 

on the rear of the fan case.

Summary of Contents for DRI-365

Page 1: ...le guards This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or i...

Page 2: ...ery mode The unit will increase in speed and supply more air to the property The unit can be boosted to obtain maximum ventilation by the operation of a boost switch 3 0 MECHANICAL INSTALLATION Succes...

Page 3: ...d correctly in the central hallway in single storey properties or in the ceiling of the top floor landing on 2 or more storey dwellings The diffuser discharges air evenly in all directions along the u...

Page 4: ...on soffit inlets FLDI150 5m length of 150mm dia insulated ducting RDC150 150mm duct connector for connecting 222 x 90 flexible duct to 150mm duct 777483 2m length insulated flexible ducting DT33 Qty...

Page 5: ...The Remote Temperature Sensor incorporates a clip in fixing bracket which can be removed for easy fitting to a suitable surface Select a suitable location for the sensor e g close to ceiling height in...

Page 6: ...house Switch supplied Speed 6 sensor supplied indicator lights 5 0 CONTROLS 5 1 Fan Speed Adjustment The unit has 6 air volume speed settings The setting switch is located on the rear of the fan case...

Page 7: ...dance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasin...

Page 8: ...8 20 05 21 Document Number 671771 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk DRI 365 Installation Manual NOTES...

Reviews: