background image

19

26. 01. 22. Document Number  671829

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS H-AT

Installation Manual

8.0 CONTROLS

The system incorporates a web enabled Trend iQ4E/96/LAN/BAC/230 
controller with iQ4/IO/8DO relay expansion module.

 
 

36 

Trend iQ4E

8.1 Controllable Items

 Supply fan.

 Extract fan.

 Heat recovery bypass damper (If applicable).

 Thermal wheel (if applicable).

 Heating coil (if fitted).

 Cooling coil (if fitted).

DX coil (if fitted).

Inlet damper (if fitted).

Exhaust Damper (if fitted).

Recirculation damper (if fitted).

8.2 Enable Signal

The unit can be enabled via the following methods:

 Software switch (ENABLE) via SDU, IQView4, IQView8 or 
network.

 Switched live (230VAC) input, PIR etc.

 Extra Low voltage contacts.

 Night cooling / summer free-cooling strategy.

 Scheduled via weekly calendar.

When the enable signal is removed, the unit will run on for a time 
defined by the run-on setpoint. If an electric heater is fitted, the fans 
will automatically run-on for an extra 2 minutes, without heating, in 
order to dissipate residual heat.

For DX units the fans will run-on for an extra 5 minutes, this is to allow 
for the ramp down of the reverse cycle compressor.

8.3 Occupancy Control

When a Trend occupancy sensor is selected via UI4 & 5 software 
module, the control will look for a Trend OCC-U sensor in the 
appropriate input. An occupied signal will give an enable signal.

0V = Occupied

14V = Unoccupied

8.4 Boost Mode

When the control receives a boost signal the fans will run at boost 
speed. Once the signal is removed the fans will run on for a time 
defined by the boost run-on setpoint.

8.5 Trickle Mode

When trickle mode is active, the fans will run at their minimum speed 
even when there is no enable signal. Heating and cooling will also 
function in this mode if available.

8.6 Constant Pressure Sensor

An extract air pressure sensor is fitted as standard. This is disabled in 
the Trend strategy by default but can be enabled by the software switch 
“Enable Constant Pressure”. 

When enabled, the unit will increase the fans speeds as required until 
the pressure differential between the extract air and atmosphere 
reaches the constant pressure setpoint. The pressure sensor is a 0-10v 
0-1000Pa sensor on the iQ4E input 6.

8.7 Filter Differential Pressure Switch

3 filter differential pressure switches are fitted as standard. These 
monitor the Extract filter, and Supply filter and Supply pre-filters.

These are connected in series with Alarm Circuit 2 (orange wires) and 
will break the circuit on overpressure. The adjustable range is 0.5 to 4 
mbar and is set by default to 2mbar.

8.8 Thermal Wheel / Plate Heat Exchanger Bypass

The plate heat exchanger bypass damper and thermal wheel both run 
on the same iQ4-8DO Relay 1. Energised = Bypass.

The bypass strategy is as follows: If the fresh air temperature is equal 
to the setpoint within the deadband, then the heat exchanger will be 
forced into bypass mode.

The 24vac bypass signal from the Trend relay is converted by relay logic 
for each of the following options:

Thermal Wheel 
Runs on a volt free enable signal, which is produced using a 
combination of the HX bypass relay and fan run relay to close the 
circuit if fans are running and the unit is not in bypass.

Plate Heat Exchanger 
The HX bypass damper opens on a 24 Vac signal which is produce 
from the bypass damper relay.

8.9 Inlet / Outlet (IO) Dampers

Inlet and outlet dampers are 24vac and controlled by the iQ4-8DO 
relay 7. When energised it gives a 24vac signal to both I/O dampers to 
open.

When installed, there is the option of connecting the internal damper 
close switch to the fault circuit alarm circuit 2 (orange wires). 

When IO dampers are fitted the strategy Switch “IO Damper Fitted” 
must be set to “On”. This will cause the software to delay the fans 
starting for the IO Damper delay period. It will also ignore faults on 
Alarm Circuit 2 if the fans are stopped and the dampers are closed 
intentionally.

8.10 CO

Control

 When a CO2 sensor is selected via UI4 & 5 function knobs, and an 
enable signal is received, ventilation will increase to reduce CO2 
concentration the target CO2 setpoint. The target CO2 sensor setpoint 
can be changed as one of the commissioning setpoints.

Summary of Contents for BPS H-AT

Page 1: ...nufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel b...

Page 2: ...ion operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50m...

Page 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Page 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Page 5: ...tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possible is pr...

Page 6: ...s EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Right hand R Access 600mm 600mm 10 Top View of Access For Right Hand Plate Heat Exchanger Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exch...

Page 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Page 8: ...ixed with the bolts provided The equipment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed befo...

Page 9: ...t the requirement of removing the roof terminal Figure 17 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Page 10: ...8 A 35 A 13 9 A 13 9 A 35 A B 20H AT 12 8 A 12 8 A 53 A 17 3 A 17 3 A 53 A B820H AT 9 6 A 9 6 A 53 A 14 1 A 14 5 A 53 A Denotes any Character These heater models require a separate power supply for t...

Page 11: ...ER UNIT Unit Isolator 21 Isolator Locations 7 6 3 Network Settings IP address 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No...

Page 12: ...ocks 24 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Page 13: ...0 8 20 Section 7 10 3 Section 7 10 4 Section 7 10 6 Section 7 10 8 7 10 Wiring Diagrams A series of basic connection wiring diagrams have been provided to assist on site wiring In order to reference t...

Page 14: ...Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 4 Unit Sizes 05 20 with Electric Heating No or CHW Cooling 31 Unit Sizes 07 22 with Electric Heatin...

Page 15: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 5 Unit Sizes 05 10 with No or LPHW Heating Reverse Cycle DX 32 Unit Sizes 07 12 with No or LP...

Page 16: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 6 Unit Sizes 15 20 with No or LPHW Heating Reverse Cycle DX 33 Unit Sizes 15 20 with No or LP...

Page 17: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 7 Unit Sizes 05 10 with Electric Heating Reverse Cycle DX 34 Unit Sizes 05 10 with Electric...

Page 18: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 8 Unit Sizes 15 20 with Electric Heating Reverse Cycle DX 35 Unit Sizes 15 20 with Electric...

Page 19: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Page 20: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Page 21: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Page 22: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Page 23: ...concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct sensor...

Page 24: ...literature is available please contact Nuaire This applies to any components not specifically mentioned in this document 9 0 MAINTENANCE It is important that maintenance checks are recorded and that t...

Page 25: ...commissioning the unit ensure that all equipment has been assembled in accordance with the installation procedure all instances where the unit is in operation the access doors should remain closed at...

Page 26: ...s See interconnection section for details No external connections are required Electric heater elements are protected by a fail safe over temperature switch which will disconnect the heater supply if...

Page 27: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Page 28: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Page 29: ...29 26 01 22 Document Number 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual NOTES...

Reviews: