Page 21
NDFL100-38 / BR003211 / Rev. 220900A
The MPA display is designed to give an indication
of the signal, the screen gives a 0 to 4 readout.
See service display screen 18
Setting the Low Gas Pressure Switch
Loss of gas pressure will cause the burner to switch
off. After a 2 minute delay the burner will reststart.
After two restarts the delay is increased to 1 hour.
This delay can be removed by electrically isolating
the burner and then re-establishing the power.
Remove the gas pressure switch cover and allow
the burner to establish main flame.
Slowly turn the adjustment dial on the gas pressure
switch clockwise until the flame is extinguished and
the burner shuts down. Turn the dial slowly
anticlockwise one division at a time until the
burner restarts and establishes main flame. Turn
the dial a further two divisions anticlockwise.
Replace the gas pressure switch cover.
F
INAL
C
HECK
Check that all the covers to components have been
replaced and that locking devices are properly
secured. Check that the appliance control
instruments are set to safe limits. On modulation
burner check and set the RWF 40.
.
3*0
(;,7
6,(0(16
/DQGLV 6WDHID5:)
%XUQHUHQDEOH
5HGXFHRXWSXW
,QFUHDVHRXWSXW
0DQXDORSHUDWLRQ
/LPLWFRPSDUDWRU
,QFUHDVHYDOXH
([LWNH\
3URFHVVYDOXHGLVSOD\UHG
6HWSRLQWGLVSOD\YDOXHJUHHQ
5HGXFHYDOXH
3*0NH\
Commissioning is now complete
Switch on the electrical supply.
The burner will now operate until switched off.
a)
by controlling instruments of the appliance
b)
manually
c)
by power failure. Upon restoration of power,
the burner will restart automatically and
follow the normal sequence.
T
HE
L
ANDIS
& S
TAEFA
M
ODULATION
C
ONTROLLER
, T
YPE
RWF 40
Basic display
The diagram below shows the RWF40 after
switching on the supply voltage. This condition is
called the basic display. The actual value and the
currently active set-point are shown here. Manual
operation, self-optimization, the operating
parameter and configuration levels can be
activated from here.
To change the working set point.
The operating display shows the actual pressure/
temperature of the boiler in red and the required
set point pressure/temperature beneath in smaller
green digits.