Table 1: Ti150C Flow rates (flow rates in usgpm)
Inlet Water Temperature (deg. F)
40 45 50 55 60 65 70
110
3.9 4.2 4.5 4.9 5.4 6.0 6.7
115
3.6 3.9 4.2 4.5 4.9 5.4 6.0
120
3.4 3.6 3.9 4.2 4.5 4.9 5.4
125
3.2 3.4 3.6 3.9 4.2 4.5 4.9
130
3.0 3.2 3.4 3.6 3.9 4.2 4.5
135
2.8 3.0 3.2 3.4 3.6 3.9 4.2
O
u
tl
e
t W
a
te
r (F
)
140
2.7 2.8 3.0 3.2 3.4 3.6 3.9
Table 2: Ti200C Flow rates (flow rates in usgpm)
Inlet Water Temperature (deg. F)
40 45 50 55 60 65 70
110
5.1 5.5 6.0 6.5 7.2 8.0 9.0
115
4.8 5.1 5.5 6.0 6.5 7.2 8.0
120
4.5 4.8 5.1 5.5 6.0 6.5 7.2
125
4.2 4.5 4.8 5.1 5.5 6.0 6.5
130
4.0 4.2 4.5 4.8 5.1 5.5 6.0
135
3.8 4.0 4.2 4.5 4.8 5.1 5.5
O
u
tl
e
t W
a
te
r (F
)
140
3.6 3.8 4.0 4.2 4.5 4.8 5.1
To avoid having too much flow at your faucets use the shut off valve after the mixing valve to limit the overall flow of domestic hot
water. Follow these instructions to achieve the best results with your Combi boiler:
1.
Open shut off valve fully.
2.
Turn the dial on the mixing valve to the desired setting
(being careful not to exceed 120˚F or a dial setting greater then 2)
and
adjust LO setting accordingly.
3.
Create the maximum amount of DHW flow that is likely to occur on a regular basis. (Usually tub faucet, or choose two other
faucets)
4.
Allow the boiler to reach steady state, and then throttle the shut-off valve until the hot water exiting the plate heat exchanger is
warmer than the mixed water exiting the mixing valve. Ensure the boiler is firing at the maximum rate, if not increase the LO
setting and repeat this step. (It is beneficial to keep the LO setting as low as possible to limit short cycling and maintain
efficiency)
7.0 WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2, and any applicable local codes. Ensure that the wiring is
in accordance with this manual.
Contact capacity of outputs C
1
or A
p
is 3 running Amps with a maximum inrush of 6 Amps.
If the capacity of the pumps is in excess
of these maximums, you must either use a pump controller, or isolation relay to energize the pumps.
Summary of Contents for Trinity Ti 100