8-2. Current Position Value Setting Data (Master to Remote Station) 

 

The master station can change the position data of VE-2CC/VM-2CC at arbitrary values by using the remote 

register (RWw) and remote output (RY). (Current position value setting)   

After setting, the remote station sends back the answer back signals by using remote inputs (RX).    The master 

station turns off the signal after checking the bit. 

 

The information of setting position data is saved in non-volatile memory which is inside of the converter;   

therefore, it is unnecessary that the current position value sets each time to turn ON the power   

supply. 

 

[Remote register RWw] 

Device No. 

Bit7 

Bit6 

Bit5 

Bit4 

Bit3 

Bit2 

Bit1 

Bit0 

RWw0(L) 

PRD7 

PED6 

PRD5 

PRD4 

PRD3 

PRD2 

PRD1 

PRD0 

RWw0(H) 

PRD15  PRD14  PRD13  PRD12  PRD11  PRD10  PRD9 

PRD8 

RWw1(L) 

PRD23  PRD22  PRD21  PRD20  PRD19  PRD18  PRD17  PRD16 

RWw1(H) 

――

 

――

 

――

 

――

 

――

 

――

 

――

 

――

 

 

 

[Remote output RY] 

Device No. 

RY07 

RY06 

RY05 

RY04 

RY03 

RY02 

RY01 

RY00 

Signal name 

――

 

――

 

――

 

――

 

――

 

――

 

――

 

ERROR 

RESET 

Device No. 

RY0F 

RY0E 

RY0D 

RY0C 

RY0B 

RY0A 

RY09 

RY08 

Signal name 

――

 

――

 

――

 

――

 

――

 

――

 

――

  PRESET 

 

 

[Remote input RX] 

Device No. 

RX0F 

RX0E 

RX0D 

RX0C 

RX0B 

RX0A 

RX09 

RX08 

Signal name 

PRESET 

ANSWER 

 

[Signal explanation] 

Signal name 

Name 

Contents 

PRD0-23 

Current position value 

setting data 

The position data can be changed to an arbitrary  value  by 

switching “PRESET” signal to “1”. (binary code: PRD0-23) 

(The data except the valid number of bits is fixed at 0.)*1 

PRESET 

Current position value 

setting input signal 

PRESET 

ANSWER 

Answer back 

The value is 1 when the current position setting is operated 

normally. 

“RRESET ANSWER” signal is 0 when “RRESET” is changed to 0. 

ERROR 

RESET 

Error clear 

An error is cleared when switching this signal to “1” by following 

method. 

- Converter diagnosis data error (ME) 

(The sensor error is automatically returned when error causes are   

removed.) 

 

 

*1: PRESET (RY08) signal should be turned OFF when the current position data and preset data are same 

value. 

The position data are changed when PRESET (RY08) signal is switched OFF to ON. 

 

  Note 

 

In the state of having a sensor error, the current position setting is not available. 

Summary of Contents for VE-2CC

Page 1: ...ZEF004410502 Specifications Instruction Manual ABSOCODER CONVERTER FOR CC Link Ver 1 10 VE 2CC VM 2CC Applicable sensor VRE P028 VRE P062 MRE 32SP062 MRE G SP062...

Page 2: ......

Page 3: ...not exposed to direct sunlight Be sure to consult with NSD when the controller is stored for long periods Do not hold the cable or shaft of ABSOCODER sensor during transport otherwise it will cause i...

Page 4: ...s at the upper right of this manual s cover page Document No Date Revision Description ZEF004410500 20 Mar 2008 1st Edition Japanese document ZEF004410206 ZEF004410501 3 Mar 2014 2nd Edition Japanese...

Page 5: ...Precautions 13 6 WIRING 14 6 1 Connection between Converter and ABSOCODER Sensor 14 6 2 Power Supply Connection 14 6 3 CC Link Connection 15 7 NOMENCLATURE and FUNCTION 16 7 1 Part Identification and...

Page 6: ...VM 2CC 1 Absolute position detection An absolute position detection format ensures accurate position detection even if a power interruption condition occurs An origin returning operation is not requi...

Page 7: ...Shaft shape flat flange mount type MRE G SP062FBC Total number of turns 64 128 160 256 320 Shaft shape key way flange mount type Extension sensor cable 4P S 0102 Standard cable cable length m 4P RBT 0...

Page 8: ...helf type within enclosure Outside dimension mm 45 W 160 H 115 D Refer to dimensions for details Mass Approx 0 7kg 2 Performance Specification Items Specifications Converter model VE 2CC VM 2CC Applic...

Page 9: ...own 4 h forward back 2 h conforms to JIS D 1601 standard Shock resistance 4 9 x 10 3 m s 2 500G 0 5 ms up down forward back X 3 times each conforms to JIS C 5026 standard Protection rating IP40 confor...

Page 10: ...h forward back 2 h conforms to JIS D 1601 standard Shock resistance 4 9 x 10 3 m s 2 500G 0 5 ms up down forward back X 3 times each conforms to JIS C 5026 standard Protection rating IP52f conforms to...

Page 11: ...6 4 DIMENSIONS 4 1 Converter VE 2CC VM 2CC Units mm...

Page 12: ...7 4 2 ABSOCODER Sensor 1 VRE P028 Units mm...

Page 13: ...8 2 VRE P062 Units mm...

Page 14: ...9 Units mm...

Page 15: ...10 3 MRE 32SP062 MRE G SP062 Units mm...

Page 16: ...11 Units mm...

Page 17: ...12 4 3 Extension Sensor Cable 3P S 0102 L 3P RBT 0102 L 4P S 0102 L 4P RBT 0102 L Units mm...

Page 18: ...hips 7 Do not install in areas where flammable and or corrosive gases are present 8 Avoid areas where splashing water oil or chemicals are likely to occur 9 Avoid areas where vibration and shocks are...

Page 19: ...than 75 mm 6 2 Power Supply Connection The power supply should be connected as described below 1 Power Supply The rush current is 10A rush time of 20ms so select the power supply after due considerati...

Page 20: ...CC Link Both sides of the unit of CC Link must be connected with the terminal resistor Connect the terminating resistance between DA to DB Wiring method Power Supply CPU CC Link master I O I O PLC VE...

Page 21: ...n SW settings of NODE and BR have an error SW setting is changed during the power supply is ON and then LED blinks SD Lights ON when sending the data RD Lights ON when receiving the data RUN Lights ON...

Page 22: ...esponse but CRC errors are found in receiving the refresh data CRC errors are found in the data address to the station Link is not started No data address exists to the station The data is not receive...

Page 23: ...data which is detected by the ABSOCODER It is communicated by using the remote register RWr Remote register RWr Device No Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 RWr0 L D7 D6 D5 D4 D3 D2 D1 D0 RWr0 H...

Page 24: ...ERROR RESET Device No RY0F RY0E RY0D RY0C RY0B RY0A RY09 RY08 Signal name PRESET Remote input RX Device No RX0F RX0E RX0D RX0C RX0B RX0A RX09 RX08 Signal name 0 0 0 0 0 0 0 PRESET ANSWER Signal expla...

Page 25: ...scan is needed more than one time after writing the current position setting data PRD0 to PRD23 Link scan time is changed according to the communication speed number of connecting units and station t...

Page 26: ...CC VM 2CC is set at 1 and 2 This is a program example when setting the current position for the station No 1 of VE 2CC VM 2CC For more details refer to the user s manual of the master unit Readout the...

Page 27: ...verter has a malfunction ME Memory error Error 1 Normal 0 A memory error has occurred At power ON The position data is indefinite state RUN LED is OFF ERROR RESET RY00 ON If the error is not cleared t...

Page 28: ...converter VE 2CC VM 2CC Connect with external device Connect ABSOCODER sensor and dedicated cable for CC Link Switch setting Set the station No and communication speed setting switch Test run Check th...

Page 29: ...rent the data link will not be available Rotation direction setting switch of ABSOCODER Sets the increased rotation direction of the current position value Factory setting all OFF Note DIP switch 2 to...

Page 30: ...ate normally if ABSOCODER is replaced VE 2CC VM 2CC has a malfunction Contact your NSD representative Is the communication cable connector disconnected Check the connection of the cable Refer to 7 3 L...

Page 31: ...e causes are as follows Sensor cables are severed The internal circuit of VE 2CC VM 2CC has a malfunction ABSOCODER has a malfunction Contact your NSD representative VE 2CC VM 2CC has a malfunction Co...

Page 32: ...KU NAGOYA JAPAN 460 8302 Distributor NSD Trading Corporation 3 31 23 OSU NAKA KU NAGOYA JAPAN 460 8302 Phone 81 52 261 2352 Facsimile 81 52 252 0522 URL www nsdcorp com E mail foreign nsdcorp com Copy...

Reviews: