NOVUS AUTOMATION
43/57
7.3.2.6
RnS PROGRAMS
This tab allows you to configure the parameters related to the programs:
QuickTune
QuickTune Mobile
RnS Programs tab
•
Program Type:
Allows you to define the type of program to be used: “Do not use programs”, “Ramp and Soak” or “Ramp and Soak Program”
(see
chapter).
PARAMETERS OF EACH PROGRAM:
Each type of program has specific parameters.
RAMP AND SOAK
•
Maximum rate of Setpoint evolution:
Allows you to define a maximum Setpoint evolution rate. Range: 0 ~ 100.
•
Dwell time at the Setpoint:
Allows you to define a dwell time at the Setpoint. Range: 0 ~ 9999.
RAMP AND SOAK PROGRAM
•
Time base for programs:
Allows you to define a time base for the programs you create: “Minutes:Seconds” or “Hours:Minutes”.
•
Type of program resumption in case of power failure:
Allows you to define the type of program resumption in case of power failure: “Resumes
at the beginning of the program”, “Resumes at the beginning of the segment”, “Resumes at the exact point where it stopped”, or “Resumes with
control disabled (
RUN
=
No
)”.
•
Program Number being Edited:
Allows you to define the number of the program to be edited. The controller allows up to a maximum of 20
programs (see
chapter).
•
Program Tolerance:
Allows you to define the maximum deviation to be allowed between the program PV and SP. If exceeded, the program is
suspended (stops counting time) until the deviation is within the tolerance set in this parameter. If set to 0, the program progresses regardless of
the difference between PV and SP.
•
Program Setpoint 0-9:
Allows you to define a Setpoint for the configured program (From Setpoint 1 to Setpoint 9).
•
Segment 1-9 Event:
Allows you to define which alarms are to be triggered during a program segment (From Segment 1 to Segment 9). Available
only for alarms whose parameter
Alarm Function 1-4
(Alarms tab) have been configured with the “Event” function.
•
Segment 1-9 Duration:
Allows you to define the duration of each of the 9 segments of the configured program (From Segment 1 to Segment 9).
Range: 99:59 (in minutes) or 0 to 9999 (in seconds), as configured in the
Program Time Base
parameter.
•
Program Link:
Allows you to create a connection between programs, using the number of the program you want to connect to. At the end of the
running program, any other program can start immediately. If set to 0, it means that there is no connection configured. See
section.
RnS TOOL SECTION:
QuickTune
has a RnS Tool, which facilitates the process of creating Ramps and Soaks programs. To use it, simply click the icon below:
RnS Tool icon
For more specific information on how this tool works, please refer to the software manual.