NOVUS AUTOMATION
22/57
dt
d
erivative
t
ime
Derivative Time. Value of the
D
term of the PID control mode, in seconds. Adjustable between 0 and 300.0 seconds.
This parameter is displayed if the
Proportional Band
is
≠
0.
(
t
c
ycle
t
ime
PWM Cycle Time. Value in seconds of the PWM cycle period of the PID control. Adjustable between 0.5 and 100.0 seconds.
This parameter is displayed if the
Proportional Band
is
≠
0.
Hyst
Hyst
eresis
Control hysteresis. Hysteresis value for Control ON/OFF mode. Adjustable between 0 and the measurement range width of the
selected input type.
This parameter is displayed only for Control ON/OFF mode (
Pb
=
0
).
Act
Act
ion
Control Logic. Only for Automatic control mode (
Ctr
>>
Auto
).
Re
– Reverse action control. Suitable for
heating
. Turns on the control output when PV is below SP.
Dir
– Direct action control. Suitable for
cooling
. Turns on the control output when PV is above SP.
Sf.st
S
of
t
S
tar
t
Soft Start function. Time interval (in seconds) during which the controller limits the control output rise rate (MV). Adjustable between
0 and 9999 seconds.
This parameter is displayed if the
Proportional Band
is
≠
0.
bias
Bias function. Allows you to change the percentage value of the control output (MV) by adding a value between -100 % and +100
%.
This parameter is displayed if the
Proportional Band
is
≠
0.
Sp.LL
S
et
p
oint
L
ow
L
imit
Allows you to set the lower limit to adjust the SP value.
Allows you to set the minimum value of the PV indication range and limit the SP adjustment for the available
linear analog inputs
(0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V).
Sp.HL
S
et
p
oint
H
igh
L
imit
Allows you to set the upper limit to adjust the SP value.
Allows you to set the maximum value of the PV indication range and limit the SP adjustment for the available
linear analog
inputs
(0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V).
ouLL
ou
tput
L
ow
L
imit
Lower limit for the control output. Allows you to set the minimum percentage value of the control output when it is set in Automatic
control mode (
Ctr
>>
Auto
) and in PID (parameter
PB
≠
0
). Typically set to 0.0 %.
ouHL
ou
tput
H
igh
L
imit
Upper limit for the control output. Allows you to set the maximum percentage value of the control output when it is set in Automatic
control mode (
Ctr
>>
Auto
) and in PID (parameter
PB
≠
0
). Typically set to 100.0 %.
iE.ou
i
nput
Err
or
ou
tput
Output value (MV1) when the controller identifies an input error.
Table 7 –
Control cycle