Program resume function. Allows you to define the behavior of the controller when returning from a power failure in the middle
of a ramps and soaks program:
Prog
– Returns at the beginning of the program
P.seg
– Returns at the beginning of the segment
t.seg
– Returns exactly where it has stopped
off
– Returns with control disabled (
RUN
=
No
).
Pr N
Pr
ogram
N
umber
Program being edited. Allows you to select the Ramps and Soaks program to be configured on the following screens of this
cycle. You can create up to 20 programs.
PtoL
P
rogram
tol
erance
Allows you to set the maximum allowed deviation between PV and SP. If exceeded, the program is suspended (stops timing) until
the deviation is within this tolerance.
The value 0 (zero) disables the function and the program progresses regardless of the difference between SP and PV.
Psp0
Psp9
P
rogram
SP
Program SPs (0 to 9). Set of 10 SP values that define the profile of the Ramps and Soaks program.
Pt1
Pt9
P
rogram
t
ime
Time of the program segments (1 to 9). Allows you to define the duration (in seconds or minutes, as set in parameter
Pr.tb
)
of each of the 9 program segments being edited.
Pe1
Pe9
P
rogram
E
vent
Event alarms (1 to 9). Allows you to define the alarms that will be triggered during a certain program segment.
The adopted alarms must be configured with the Event Alarm (
rS
) function (see
section).
Lp
L
ink
P
rogram
Program link. Allows you to connect one program to another. If set, another program can start after the first program has run.
NONE
– Does not connect the current program to any other program
1 to 20
– Connects the current program with the selected program number
Table 13 –
Program cycle