NOVUS AUTOMATION
30/57
4.3.9
TIMER CYCLE (
CFG
>>
tm
)
This is the Timer Cycle:
Timer cycle
t.Str
T
imer
St
art
Starts the timer. Allows you to set the timer start mode:
oFF
– Disabled
SP
– Starts counting when the PV value reach the SP value
F
– Starts counting when you press the key
RUN
– Starts counting when control is enabled (
RUN
=
YES
)
DI
– Triggers with digital input
t.dir
T
imer
Dir
ection
Counting mode. Allows you to set the timer counting mode:
Dn
– Backward mode
uP
– Forward mode, starting from zero
t.tb
T
imer
t
ime
b
ase
Timer time base. Allows you to set the timer time base:
MM
:
SS
– Time base in minutes:seconds
HH
:
MM
– Time base in hours:minutes
T1
T
imer
1
t1
time base. Allows you to set a time base for timer 1. Range: 00:00 to 99:59 (HH:MM or MM:SS, as set in parameter
t.tb
).
T1.E
T
imer
1 E
nabled
If set to
yes
, allows the Timer 1 parameter (
t1
) to be displayed (and set) in the Operation Cycle. See
section.
t.end
T
imer
End
Allows you to set the behavior of the output
T1
when
T1
timer is expired.
oFF
– Turns off the output at the end of the timer
on
– Turns on the output at the end of the timer
T2
T
imer
2
T2
time base. Allows you to set a time interval at which
T2
output will remain on after T1 has expired. Range: 00:00 to 99:59
(HH:MM or MM:SS, as set in parameter
t.tb
).