This is the Control Cycle:
Control mode
This cycle allows you to configure the parameters that refer to the control mode and the device tuning process. See
chapter for
more information about PID control and tuning processes.
Atun
A
uto-
tu
ne
Allows you to define the tuning mode to be used:
off
– Disabled
Fast
– Fast auto-tuning
FULL
– Precise auto-tuning
seLf
– P auto-adaptive tuning
rsLf
– Forces a new p auto-adaptive auto-tuning
TGHt
– Forces a new p auto-tuning when
RUN
=
YES
or when the controller is on
pb
P
roportional
B
and
Proportional Band. Value of the
P
term of the PID control mode, in percent of the input type maximum range. Adjustable between
0 and 500.0 %.
When set to 0.0 (zero), determines the ON/OFF control mode.
ir
i
ntegral
r
ate
Integral Rate. Value of the
I
term of the PID control mode, in repetitions per minute (Reset). Adjustable between 0 and 99.99.
This parameter is displayed if the
Proportional Band
is
≠
0.