~ 14 ~
UBZ-304
NOVATEK-ELECTRO
Motor remote start and
shutdown via
RS-232/RS485 interface
MotorOp
RS-2/5
0
2
0
0
–
"Off"
–
remote control is
disabled;
1
–
"OnSta"
–
remote control is
enabled; motor start after UBZ
energizing is enabled after ARS
time;
2
–
"OffSt"
–
remote control is
enabled, motor start after UBZ
energizing is disabled until the
command for remote energizing
200
Temperature control
Permit for temperature
control and type of
temperature transmitter 1
Temp S1
Type
0
2
0
0
–
"Off "
–
it is disabled;
1
–
"R>1.7"
–
it is of motor built-in
type (protection is enabled if the
transmitter resistance is above
201
Table 3.6 (Continued)
Settings and readings
Parameter
on LCD
Min.
value
Max.
value
Factory
setting
Message on LCD, actions
Address
1.7 kOhm);
2
–
"PTC"
–
PTC (1kOhm at
25°С)
Motor trip temperature
Temp S1
Off M
0
100
80
202
Temperature correction
of the first transmitter
Temp S1
Corr
-9
9
0
203
Permit for temperature
control and type of
temperature transmitter 2
Temp S2
Type
0
3
0
0
–
"Off "
–
it is disabled;
1
–
"Pt100"
–
of Pt100 type;
2
–
"Ni100"
–
of Ni100 type;
3
–
"Ni120"
–
of Ni120 type.
204
Motor trip temperature
Temp S2
Off M
0
220
180
205
Warning temperature
Temp S2
Alarm
0
220
170
206
Temperature correction
of the second transmitter
Temp S2
Corr
-9
9
0
207
ARS after tripping
Temp AR
0
1
1
0
–
"Off"
–
ARS is disabled;
1
–
"On"
–
ARS is enabled.
208
Temperature
transmitters fault
reaction
Temp Sens
Fault
0
1
0
0
–
"AonM"
–
warning and
continuation of operation;
1
–
"AoffM"
–
warning and motor
stop.
209
Motor insulation resistance
Protection for the motor
minimum insulation
resistance
Insulation
Mr
0
4
1
0
–
"Off"
–
it is disabled;
1
–
"5 AR"
–
motor is not enabled
when insulation resistance is less
than 500 kOhm, ARS is enabled;
2
–
"10 AR"
–
motor is not enabled
when insulation resistance is less
than 1000 kOhm, ARS is enabled;
3
–
"5 nAR"
–
motor is not enabled
when insulation resistance is less
than 500 kOhm, ARS is disabled;
4
–
"10nAR"
–
motor is not
enabled
when
insulation
resistance is less than 1000
kOhm, ARS is disabled.
210
Miscellaneous
Activating the mode of
minimum number of
settings
Minimal set
0
1
1
0
–
"Off"
–
the mode is disabled;
1
–
"On"
–
the mode is enabled.
The mode change is possible only
in advanced user
level
mode
211