~ 10 ~
UBZ-304
NOVATEK-ELECTRO
Table 3.5 (Continued)
Measurement functions
Range
Accu-
racy
Mnemonic
Address Data transfer
units
Cosine of angle between voltage and phase
current L3
0
–
1
5%
Cos C
68
Temperature of transmitter 1
5
, °C
minus 40
–
80
1°C
Temp
dat 1
69
5000
–
transmitter is off
1000
±
10
–
s.c.
of transmitter
2000
±
10
–
transmitter
breakout
Temperature of transmitter 2
5
, °C
minus 40
–
220
1°C
Temp
dat 2
70
Current value at analogue input "4-20 mA", mA
0
–
25
2%
Input i
71
1/100 mA
Voltage value at analog input "0-10 V", V
0
–
10
2%
Input U
72
Tenths of Volt
Full electric power
6
, kVA/h
0
–
200000000
5%
ApE
90
91
‘00
W/h
Active electric power
6
, kW/h
0
–
200000000
5%
AcE
92
93
Reactive electric power
6
, kVA
r
/h
0
–
200000000
5%
ReE
94
95
Notes:
1
If the insulation resistance of the motor is more than 20 MOm, then the value indicator displays code
“
>20M
“.
When
the motor is running (energized motor) the insulation resistance is not defined and the code indicator displays “
---
“(
when
measuring circuit of motor insulation connecting).
2
If ARS is disabled, the indicator displays
“not”.
3
If the time before shutdown by thermal overload protection or waiting time before permit to start-up is not defined
(more than 900 s), then the value indicator displays code
“undef“.
If the protection function is disabled, the indicator
displays
“not”.
4
If the power consumed by the load is more than 999 kW (kVA, kVA
r
), the values of power are displayed with MW
(MVA, MVA
r
).
5
If the temperature value exceeds specified limits, then the indicator displays the alarm code in accordance with table
5.13. If the temperature sensor is disabled by software, then the indicator instead of temperature values displays
“
Off
”.
6
In excess of the energy meter of the value 200 000 000, the counter is reset and the energy metering will start from
zero. Recording the current values of the energy in the non-volatile memory is performed every 15 min.
3.3 PROGRAMMABLE PARAMETERS
Programmable parameters and their variation limits are given in Table 3.6.
Table 3.6
–
Programmable Parameters
Settings and readings
Parameter
on LCD
Min.
value
Max.
value
Factory
setting
Message on LCD, actions
Address
Set the current time
Real Time
Setting of current time and date
(it. 5.2.8)
See Table
5.10
Transformers
Rated output current of
used CT, A
CT out i
1
5
5
151
Rated current of CT, A
CT nom i
20
800
100
152
Basic parameters
Rated current of motor,
A
Rated
Inо
m
0
630
0
0
–
current is not set: UBZ will not
enable the load relay (it. 5.1.5.7).
150
Time during which the
average current is
measured, s
Tm average
i
10
600
60
Time during which the average
current is measured (parameters:
"Average
i1",
"Average
i2",
"Average i3" of Table 3.5).
153
Over-current protection
Type of over-current
protection
Type
Imax
0
5
0
0
–
"Indep" - protection with
independent time delay.
Types
of
protection
with
dependent time delay:
1
–
"SIT" ; 2
–
"VIT (LTI)";
3
–
" EIT"; 4
–
"UIT"; 5
–
"RI".
154
Actuation setting for
over-current protection,
Imax coef
0.8
9
4
Repetition factor is set relative to
rated motor current (it is used at
155