background image

- 3 - 

NOVATEK-ELECTRO

                                                                                     REV-201М

     

                                                                                                                                                       

 

This present manual contains necessary information about application, main operation principles and 

adjustment setting for the two-channel electronic time delay relay REV-201M (hereinafter REV-201

М). 

 

1  GENERAL DESCRIPTION AND OPERATION 

 

1.1  APPLICATION 

 

REV-201M  is  designed  for  the  commutation  of  electrical  circuits  of  240V  50Hz  AC  as  well  as  24 

– 100V DC 

electrical circuits with the adjustable time delay setting.  

The relay has two channels and can be operated by one of seven operation algorithms that the user specifies: 

-

 

Turn

 ON

 time delay relay; 

-

 Pulse relay 1;

 

 

-

 Intermittent relay 1; 

-

 Operation relay *.  

-

 Pulse relay 2; 

-

 Intermittent relay 2; 

-

 Off-delay relay. 

 

* REV-201M could be used as the relay of pre-starting signalization for the machinery that require to announce 

that some mechanism or machinery will soon take a start to make people aware of this and get away from the risky 
zones.  Widely  used  for  steel  plants,  heavy  machinery,  cranes  and  construction  mechanisms  as  well  as  mining 
companies for the technological stuff safety. 

 

Time  delay  setting  for  each  channel  starts  from  the  moment  of  the  power  supply  given  to  the  corresponding 

channel. REV-201M allows to provide 2 modes of operation: 

Mode 1. Independent operation of channels.

 To each of two channels power supply is given independently 

and thus each channel starts the countdown from the moment the power supply is given. This is the mode when 2 
independent time relays are functioning in one compact case housing (2 time delay relays in one case). 

Mode  2.  Parallel  operation  of  the  channels.

 

To  each  of  two  channels  the  power  supply  is  applied 

simultaneously. Thus the time countdown on each channel starts at the same time and comes one and the same input 
power supply. Triggering time corresponds to the user-adjusted settings for each of the channels. So the REV-201M in 
this mode operates like one time delay relay with 2 output contacts that have the same or different time settings. 

ATTENTION!!!  The power supply of both channels must necessarily have common neutral. 

 

1.2

 

FIRMWARE VERSIONS AND CHANGES 

 

10.10.2007  V1  

First released version

  

12.09.2014  V2  Timeslot are changeed (timeslot are multiple

 

10). 

                          

Two operation algorithms were added: “Pulse 2” and “Intermittent 2”. 

03.03.2016  V3  

The operation algorithm of “Turn-off Delay” was added. 

 
1.3  TECHNICAL PARAMETERS 

 

1.3.1

 Basic technical characteristics are shown below in Table 1. 

 

     Table 1 

 

Rated AC input power supply (terminals L, N), V 

150 

– 300 

Voltage Harmonicas Distortion Factor, not more than 

12 % 

Rated DC input power supply (terminals  +24, N), V 

24 

10% 

Rated power circuit frequency, Hz 

50 

– 60 

  Harmonical configuration (nonsinusoidality) of power supply voltage  

EN 61000-3-2  
(IEC 1000-3-2) 

Initialization  readiness  time  after  the  power  supply  application  to  the  channel, 
sec, less then 

0,25 

Timing accuracy, %, not less then 

1,5 

Time setting accuracy (scale accuracy), %, not less then 

Number of operation algorithms 

The time setting range is divided in 8 subsections 
 

T1

 

T2

 

0-1 s 
0-10 s 
0-100 s 
0-1 min 
0-10 min 
0-100 min 
0-1 hour 
0-10 hours 

0-10 s 
0-100 s 
0-1 min 
0-10 min 
0-100 min 
0-1 hour 
0-10 hours 
0-20 hours 

Summary of Contents for REV-201?

Page 1: ...NOVATEK ELECTRO Ltd Intelligent industrial electronics MULTIFUNCTIONAL TWO CHANNEL TIME DELAY RELAY REV 201 OPERATING MANUAL Review the Operating manual before using the unit www novatek electro com...

Page 2: ...PT TO REMOVE AND REPAIR THE UNIT Some of the unit components may be live NEVER ATTEMPT TO OPERATE THE UNIT WITH THE MECHANICAL DAMAGE OF THE HOUSING The unit is not designed for operation under impact...

Page 3: ...ioning in one compact case housing 2 time delay relays in one case Mode 2 Parallel operation of the channels To each of two channels the power supply is applied simultaneously Thus the time countdown...

Page 4: ...more then 0 150 Outer dimensions Figure1 Operation temperature range from 30 to 55 Storage temperature from 45 to 60 Arbitrary mounting position Standard 35 mm DIN rail mounting Electrical characteris...

Page 5: ...the power supply source is applied to the input terminals L1 N Channel 1 L2 N Channel 2 Time delay setting is selected using the knobs of potentiometers 3 5 10 12 figure 1 Each channel has two adjusta...

Page 6: ...further Note if the time interval of potentiometer 2 is equal to zero the load relay will not switch over 1 3 3 4 Control pre starting signalization operation function Figure 5 The working algorithm o...

Page 7: ...ED of this channel is on and the time reading begins T1 T2 After delay time period the load relay switches off the LED changes the light to green and the relay turns in standby mode The restart of rel...

Page 8: ...s mode the supply voltage of the second channel is used as the main power supply for the relay and the power input of the first channel is used as the control signal 2 GENERAL USE AND APPLICATION 2 1...

Page 9: ...this time interval T1 the relay contacts get open and starts the timing countdown of set time interval T2 After the termination of the T2 timing countdown REV 201M starts and the process keep on work...

Page 10: ...t is strictly prohibited to use simultaneously both power supply inputs for 24V DC and mains 230 240 VAC Only one power supply input should be used 2 2 USAGE AND OPERATION OF REV 201M Connect the powe...

Page 11: ...shall provide a free repair of the unit within the warranty period if all the provisions of user manual were complied with by the consumer The unit shall not be subject to warranty service in the foll...

Reviews: