Document 51996 AFP-300/400 NION  Installation Rev. A1  03/04/03

3. Check the 

Backup screen database

 option if you wish to create a backup copy of the old screen

database file.  The backup will be saved as “screen.bak” and will be located in the same directory where
the utility was run.  This directory will normally be c:UniNet\PlugIns\screen.bak.
Select the name of the site you wish to convert by choosing from the drop-down list.
In the 

Select node to convert

 list, only NION-232 PCB board 300/400 nodes will be displayed as

options for upgrading.  In addition, any 300/400 nodes that have previously been converted will not be
displayed in this list.
Once you have selected the desired 300/400 node, specify the 

Panel Node Number

.  This is the

network node number programmed in the fire panel.

Figure A-3:  Performing the Conversion Upgrade

Once these parameters have been defined, click on 

Next 

to continue with the upgrade.  The utility will prompt you

to verify the information entered.  Once this is done, the utility will finish the upgrade process, and a message
saying “Upgrade complete” will be displayed.

IMPOR

IMPOR

IMPOR

IMPOR

IMPORTTTTTANT

ANT

ANT

ANT

ANT:  It is imperative that the correct panel node number be

:  It is imperative that the correct panel node number be

:  It is imperative that the correct panel node number be

:  It is imperative that the correct panel node number be

:  It is imperative that the correct panel node number be

entered during the conversion process.  F

entered during the conversion process.  F

entered during the conversion process.  F

entered during the conversion process.  F

entered during the conversion process.  Failure to do so will result in

ailure to do so will result in

ailure to do so will result in

ailure to do so will result in

ailure to do so will result in

device ID errors in the converted database.

device ID errors in the converted database.

device ID errors in the converted database.

device ID errors in the converted database.

device ID errors in the converted database.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for UniNet 2000 AFP-300 NION

Page 1: ...truction Manual AFP 300 400 NION Document 51996 03 04 03 Rev A1 Version2 51996 A1 ECN 03 047 51996 A1 ECN 03 047 51996 A1 ECN 03 047 51996 A1 ECN 03 047 51996 A1 ECN 03 047 Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...2 Document 51996 AFP 300 400 NION Installation Rev A1 03 04 03 Technical Manuals Online http www tech man com firealarmresources com ...

Page 3: ...escaping gas improper storage of flammable mate rials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detec tors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a q...

Page 4: ...modifica tions verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal re moval Though designed to last many years system components can fail at any time This system contains static sensitive c...

Page 5: ...CA Style 7 Transceiver 16 Figure 1 12 FOXC PCA and DFXC PCA Fiber Optic Network Transceivers 16 1 9 Serial Connections with the AFP 300 400 Control Panel 17 Figure 1 13 AFP 300 400 NION AFP 300 400 Panel Wiring Diagram 17 1 10 Software Replacement Upgrade Installation 18 Figure 1 14 NION Software Replacement 18 1 11 EVENT REPORTING FORMAT 19 Section 2 The AFP 300 400 NION Explorer Plug In 21 2 1 A...

Page 6: ...work Installation Manual 51539 UniLogic 51547 Workstation 51540 Event Manager 51546 System Utilities 51592 UniTour 51550 BCI ver 3 3 51543 AFP 300 400 Operation Manual 50260 Local Area Server 51544 Wide Area Server 51545 Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...ION is a plug in component of the UniNet Workstation It allows a workstation to view events and other data originating from the AFP 300 or AFP 400 fire alarm control panels UniNet consists of graphical workstations monitoring and controlling local or remote twisted pair or fiber optic networks Remote network monitoring is achieved through the use of a Building Communications Interface BCI which ha...

Page 8: ...8 Document 51996 AFP 300 400 NION Installation Rev A1 03 04 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 9: ... older AFP When upgrading from the older AFP When upgrading from the older AFP When upgrading from the older AFP 300 400 NION 232B board the database conversion utility 300 400 NION 232B board the database conversion utility 300 400 NION 232B board the database conversion utility 300 400 NION 232B board the database conversion utility 300 400 NION 232B board the database conversion utility needs t...

Page 10: ...d Fault Detection Ground Fault Detection Ground Fault Detection Ground Fault Detection Ground Fault Detection GND 24VDC P P P P Power Input TB5 ower Input TB5 ower Input TB5 ower Input TB5 ower Input TB5 P2 Serial Interface B P2 Serial Interface B P2 Serial Interface B P2 Serial Interface B P2 Serial Interface B NUP P NUP P NUP P NUP P NUP Port EIA ort EIA ort EIA ort EIA ort EIA 232 232 232 232 2...

Page 11: ...nge of 0ºC to 49ºC 32 F 120 F 93 humidity non condensing at 30ºC 86 F 1 4 Cabinet Mounting Information The AFP 300 400 NION board can be installed in any NOTIFIER CAB 3 or CAB 4 series cabinet a NOTIFIER NISCAB 1 or an ABS 4DB Annunciator Backbox surface mount The NISCAB 1 allows the installa tion of one NION The AFP 300 400 NION board is designed to be installed on a wall within 20 feet in condui...

Page 12: ...nclosure be sure to use the inboard set of four mounting studs ABS 4D B Installation The Annunciator Backbox ABS 4D B cabinet has a hinged door with a key lock to diminish unauthorized use and a transparent window The mounting panel and door are both hinged at the bottom for easy access Power must be supplied externally if the cabinet is surface mounted Knockouts are provided for use with a 1 2 in...

Page 13: ...ates the NION is operating properly NION Status Indicates status of the NION Rapid blinking indicates proper NION operation On or Off indicates critical error and that the NION is not functioning 1 6 NION Power Requirements The AFP 300 400 NION requires 24VDC 250 mA nominal and supervised battery backup in accordance with local code requirements It can be powered by any regulated power limited sou...

Page 14: ... cable UL listed for use in a power limited fire detection system if used in conjunction with a fire monitoring network Riser plenum or non plenum cable according to local fire alarm wiring codes FOXC The FOXC transceiver is used for point to point optical fiber For the FOXC two strands are required per segment one dedicated to transmit the other to receive The FOXC can have no more than 8db of at...

Page 15: ...Network Transceiver The S7FTXC PCA combines two FT 10 interface ports that allow the transceiver to meet Style 7 wiring requirements The two ports on the S7FTXC PCA when used with true style 7 wiring requirements create a point to point type network segment allowing up to 8 000 feet between nodes that use the S7FTXC PCA The seperate FT ports allow two twisted pair connections so that a cabling fau...

Page 16: ...7FTXC Style 7 FT 10 Transceiver Header Connection Port 1 Port 2 Packet LED Status LED Port 1 Error LED Port 2 Error LED Opposite side of S7FTXC Termination Jumper Port 2 Termination Jumper Port 1 Bus Termination FT Termination Bus Termination FT Termination NOTE See section 1 1 8 of the Network Installation manual for more information about FT and Bus termination DFXC DFXC DFXC DFXC DFXC Dual Fibe...

Page 17: ...AFP 300 400 manual for more information on programming panel node addresses The NION operates at 2400 baud 8 data bits no parity and 1 stop bit In order to utilize all features available with the AFP 300 400 the AFP 300 400 Plug In utility must be configured at the system Workstations General Plug In setup information can be found in the Workstation manual AFP AFP AFP AFP AFP 300 400 300 400 300 4...

Page 18: ...irectly handling the AFP when directly handling the AFP 300 400 NION or any other hardware 300 400 NION or any other hardware 300 400 NION or any other hardware 300 400 NION or any other hardware 300 400 NION or any other hardware 2 Place the flash modules in their respective sockets according to the figure below Orient the notch on the chip with the notch in the socket 3 Re apply power to the NIO...

Page 19: ...Mmmm module Annunciators ANNUNaa aa annunciator Annunciator Points AaaPppp aa annunciator ppp point Bell Circuits BC cc cc circuit Panel Circuits PC cc p cc circuit p point Zones ZONEzzz zzz zone Panel Panel Ground GROUND Battery BATTERY AC Power ACPOWER Audibles Audible Example 1 Echelon Node 001 AFP 300 400 Panel programmed as node 007 Loop 02 Detector 003 reports with the following device ID 00...

Page 20: ...20 Document 51996 AFP 300 400 NION Installation Rev A1 03 04 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 21: ...o the Workstation Configuration menu and then select NION Applications Locate the NION Type drop down box Using this drop down box scroll down and select AFP 400 SPB Click the Change button on the form This will cause a dialogue box to be displayed with the names of all available configuration files Select 400SPB cfg then click the Open button Finally click Done to end the registration process 2 F...

Page 22: ... report a corresponding event Deactivate accessible for SLC Output Panel Circuit or Zone This will manually deactivate the specified device and the workstation will display a system message reporting the action Clear Panel History This remotely clears the AFP 300 400 s history The history is stored inside the AFP300 400 as a sequence of characters and is not accessible to the plug in Clear Verific...

Page 23: ...llowing into consideration 1 Some events are double ended or paired in that they have both normal and off normal conditions For example Input On and Input Off are paired events 2 Some events are single ended in that they only have one way of reporting For example Card Accepted is a single ended event because it has no associated paired event hence no off normal to normal condition 3 Some events ar...

Page 24: ...ommand will download the database from the panel to the NION software application Update All If a Configurable Event Status has been modified clicking in this command will update any changes made to configurable devices Cancel All If changes have been made and you change your mind Cancel All will cancel any changes 2 4 Viewing the Silenced Panels List The UniNet 2000 workstation displays a list of...

Page 25: ...ch the new format used by this NION device IDs in the screen database to match the new format used by this NION device IDs in the screen database to match the new format used by this NION device IDs in the screen database to match the new format used by this NION device IDs in the screen database to match the new format used by this NION Any UniL Any UniL Any UniL Any UniL Any UniLogic ogic ogic o...

Page 26: ... conversion process It is recommended that the you perform the upgrade using the default file path for the screen mdb file specified in the Database to convert field Click on Next to continue or Cancel to abort the upgrade process Figure A 2 The Database Upgrade File Path Technical Manuals Online http www tech man com firealarmresources com ...

Page 27: ...mpt you to verify the information entered Once this is done the utility will finish the upgrade process and a message saying Upgrade complete will be displayed IMPOR IMPOR IMPOR IMPOR IMPORT T T T TANT ANT ANT ANT ANT It is imperative that the correct panel node number be It is imperative that the correct panel node number be It is imperative that the correct panel node number be It is imperative ...

Page 28: ...28 Document 51996 AFP 300 400 NION Installation Rev A1 03 04 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 29: ... Launching 21 Registration 21 C CAB 3 CAB 4 Series Installation 11 Cabinet Mounting 11 Configuration AFP 300 400 Control Panel 17 Configuring the AFP 300 400 Control Panel 17 D Database Conversion Utility 25 Running 25 DFXC 14 DFXC Transceiver 14 Diagnostic LEDs 13 E EVENT REPORTING FORMAT 19 Event Status 25 F Fault Annunciation 13 fiber optic cable 14 FOXC 14 FOXC Transceiver 14 FTXC 14 FTXC Tran...

Page 30: ...ION Board Layout 10 AFP 300 400 NION Connectors 11 AFP 300 400 NION Description 9 AFP 300 400 NION Diagnostic LEDs 13 NISCAB 1 Installation 12 P PC Board Layout 10 PC Boartd Connectors 11 Power Connections 17 Power Requirements 13 R Relay Output 13 Required Components 11 S SMX Network Connection 14 SMX Transceivers 14 Software Replacement 18 Style 7 Network Transceiver 15 T Transceivers 14 Network...

Page 31: ...31 Document 51996 AFP 300 400 NION Installation Rev A1 03 04 03 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 32: ...2 Clintonville Rd Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that NOTIFIER is not an insurer and assumes no ri...

Reviews: