19
Document 51996 AFP-300/400 NION Installation Rev. A1 03/04/03
1.11 EVENT REPORTING FORMAT
All Event reporting from the AFP-300/400 NION appears at the Workstation in the following format:
NNNSSSXXXXXXXX
Where
NNN
is the network node number for the AFP-300/400 NION.
Where
SSS
is the node number programmed in the AFP-300/400 panel.
Where
XXXXXXXX
is an 8 digit device ID.
The 8 digit ID will conform to one of the following formats, depending on the nature of the device.
87654321
Detectors:
LllDddd
Lll = loop, Dddd = detector
Modules:
LllMmmm
Lll = loop, Mmmm = module
Annunciators:
ANNUNaa
aa = annunciator
Annunciator Points:
AaaPppp
aa = annunciator, ppp = point
Bell Circuits:
BC cc
cc = circuit
Panel Circuits:
PC cc-p
cc = circuit, p = point
Zones:
ZONEzzz
zzz = zone
Panel:
Panel
Ground:
GROUND
Battery:
BATTERY
AC Power:
ACPOWER
Audibles:
Audible
Example 1:
Echelon Node 001, AFP-300/400 Panel programmed as node 007, Loop 02, Detector 003 reports with the
following device ID:
001007 L02D003
Example 2:
Echelon Node 007, AFP-300/400 Panel programmed as node 003, Bell Circuit 01 reports with the following
device ID:
007003 BC 01
Example 3:
Echelon Node 003, AFP-300/400 Panel programmed as node 001, Zone 004 reports with the following device
ID:
003001 ZONE004