16
Document 51996 AFP-300/400 NION Installation Rev. A1 03/04/03
Figure 1-11: SMX Transceivers: S7FTXC-PCA Style 7 Transceiver
FOXC-PCA and DFXC-PCA Fiber Optic Network Transceivers
The FOXC-PCA allows up to 8db of attenuation between nodes in a point to point configuration only.
The DFXC-PCA can operate in either a bus or a ring format. The regenerative properties of the DFXC transceiver
allow runs of up to 12db of attenuation between each node, with up to 64 nodes per segment.
S7FTXC
S7FTXC
S7FTXC
S7FTXC
S7FTXC
Style 7 FT-10 Transceiver
Header Connection
Port 1
Port 2
Packet LED
Status LED
Port 1 Error LED
Port 2 Error LED
Opposite side of S7FTXC
Termination Jumper
( Port 2)
Termination Jumper
(Port 1)
Bus Termination
FT Termination
Bus Termination
FT Termination
NOTE: See section 1.1.8 of the Network
Installation manual for more information
about FT and Bus termination.
DFXC
DFXC
DFXC
DFXC
DFXC
Dual Fiber Optic Transceiver
FOXC
FOXC
FOXC
FOXC
FOXC
Fiber Optic Transceiver
Header Connection
Header Connection
ST Style TX Connection
ST Style RX Connection
ST Style Connection
Figure 1-12: FOXC-PCA and DFXC-PCA Fiber Optic Network Transceivers
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com