62
INA 15092:I 05/30/01
Refer to
Figure 2.1-1
for a flow chart of the of the Partial System Programming menu. Detailed information on the Partial
System Programming menu options follows.
1=NFN -
NOTIFIRENET
D }X1X1X
Option 1 from the Partial System Programming menu allows the user to program the INA, change the
NOTIFIRENET
node address, select the network configuration, or select the communication threshold for the MIB-W or MIB-WF. The
INA may be autoprogrammed to include all nodes on the network in its group or manually programmed to include only
selected nodes. For more information on INA groups and autoprogramming, refer to
About Groups and Linking
in Chapter
Two of this manual.
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG : 1
PRESS 1=NFN,2=KEY,3=CABLE,4=ANN,5=UDACT,6=EXTEQ,7=LOCP : 1
DO@YOU@WANT@TO@CHANGE@THE@NFN@ADDRESS?@(Y=YES,@N=NO)@@@@@@@@@@@@@@@@@@@@:@Y
ENTER@THE@ADDRESS@(1-240)@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@
:@211
DO@YOU@WANT@TO@CHANGE@THE@MIB-W@THRESHOLD@FOR@CHANNEL@A?@@@@@@@@@@@@@@@@:@Y
ENTER@THE@MIB-W@THRESHOLD@FOR@CHANNEL@A@(H=HIGH,L=LOW)@@@@@@@@@@@@@@@@@@:@H
DO@YOU@WANT@TO@CHANGE@THE@MIB-W@THRESHOLD@FOR@CHANNEL@B?@@@@@@@@@@@@@@@@:@Y
ENTER@THE@MIB-W@THRESHOLD@FOR@CHANNEL@B@(H=HIGH,L-LOW)@@@@@@@@@@@@@@@@@@:@L
DO@YOU@WANT@TO@CHANGE@MIB@DATA@PORT@USAGE@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@@:@Y
DO@YOU@WANT@TO@USE@BOTH@MIB@DATA@PORTS?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@@@@:@Y
DO YOU WANT TO CHANGE THE NETWORK MAP (Y=YES,N=NO) : Y
DO YOU WANT TO AUTOPROGRAM THE INA FOR THE CURRENT NETWORK? (Y=YES,N=N) : N
IS NODE 002 TO BE ADDED/DELETED TO THE NETWORK MAP (Y=ADDED,N=DELETED) ; Y
IS NODE 003 TO BE ADDED/DELETED TO THE NETWORK MAP (Y=ADDED,N=DELETED) : Y
A unique address must be assigned at each node in the network. Using both MIB data ports changes the network to a
Style 7 operation.
Note:
Programming steps will be aborted if any new events are received by the INA.
2=KEY - Keyswitch
D }X1X2X
Option 2 from the Partial System Programming menu allows the programmer to enable or disable the INA keyswitch input.
When the keyswitch is enabled and in the OFF position, the INA keypad will
not
accept user input. If the keyswitch is
enabled and in the ON position, the keypad
will
accept input. When the keyswitch is disabled, the keypad is always ready
to accept user input.
To enable the keyswitch, install the shunt on only one terminal of Connector J3. To disable the keypad without using the
keyswitch, install the shunt plug across both terminals of Connector J3 on the INA . For more information on the keyswitch
and shunt plug, refer to Chapter One,
Section 2.2.2
of this manual.
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7MSG : 1
PRESS 1=NFN,2=KEY,3=CABLE,4=ANN,5=UDACT,6=EXTEQ,7=LOCP : 2
DO@YOU@WANT@THE@KEYSWITCH@ENABLED?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@@@@@@@@@:@Y
3=CABLE - Power Supervision Cable
D }X1X3X
Option 3 from the Partial System Programming menu allows the programmer to enable or disable the INA power supervision
cable. When the power supervision cable is enabled, the INA will supervise the main power supply. When the power
supervision cable is disabled, the INA will not supervise the main power supply. If the INA is sharing a power supply with
an AM2020/AFP1010 panel, the power supervision cable should be disabled because the AM2020/AFP1010 supervises the
main power supply.
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG : 1
PRESS 1=NFN,2=KEY,3=CABLE,4=ANN,5=UDACT,6=EXTEQ,7=LOCP : 3
DO@YOU@WANT@THE@POWER@SUPPLY@CABLE@ENABLED?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@ : Y