HS-NCM Installation Document —

 P/N 54014:B2 04/25/2014

13

7 Diagnostic Indicators 

The HS-NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system connection. Refer to 
Table 5 for a list of diagnostic indicators and their descriptions. Refer to Figure 11 for diagnostic indicator locations.

HS

-NCM-

LE

D

S

.wmf

Figure 11  Diagnostic Indicator Locations

NUP A TX
NUP A RX
NUP B TX
NUP B RX

PWR

WDT

PWR FAIL

PROGRAM

USB A

LINK B

DATA B

NFN B

DATA A

NFN A

LINK A

ACTIVE

USB B
ENET TX (10/100)
ENET RX (10/100)

Summary of Contents for HS-NCM

Page 1: ...and assembly name can be found on the fire panel s circuit board NUP Port connections are still required for communication between the HS NCM and the fire panel One HS NCM can provide network communic...

Page 2: ...p to two fire alarm control panels and a programming computer Enables software and database upload download over High Speed Noti Fire Net Communication Circuit Voltage and Current Rating Protocol TB4...

Page 3: ...5 dB limit 9 125 micrometers single mode 30 dB limit Wavelength 1 1310 nanometers Fiber Connectors LC style Data is regenerated at each node Two network ports to allow simultaneous connection of up t...

Page 4: ...terminal wiring with strain relief Data is regenerated at each node Two network ports to allow simultaneous connection of up to two fire alarm control panels and a programming computer Enables softwa...

Page 5: ...wer source 2 Connect VeriFire Tools to the network or directly connected to the HS NCM 3 In VeriFire Tools access the Upload Download Screen 4 In the Network Node Session of the Upload Download screen...

Page 6: ...Installation Document P N 54014 B2 04 25 2014 7 Select HS NCM Parameters 8 The HS NCM Parameters screen will be displayed listing HS NCM defaults HS NCM context menu jpg HS NCM UPDL jpg HSNCMPARMSFOR...

Page 7: ...on code for the HS NCM Not user modifiable Port A Mode For HS NCM MF HS NCM SF and HS NCM MFSF Port A Mode is not applicable for Fiber ports Port A Mode will automatically be configured as Fiber and c...

Page 8: ...M MFSF CHS 4L 4N CHS2 M3 CHS M3 the NFS2 640 chassis or NFS 320 enclosure Mount the HS NCM in standard option module positions as described in your control panel installation manual Figure 4 shows CHS...

Page 9: ...egarding these devices refer to the documentation listed in Table 6 Supplemental Documentation NOTE The module cannot be mounted in the ADP 4B Dress Panel when a front slot of the CHS 4 or CHS 4N is o...

Page 10: ...h the HS NCM TB4 1 CH A Channel A Driver Receiver TB4 2 CH A Channel A Driver Receiver TB5 1 CH B Channel B Driver Receiver TB5 2 CH B Channel B Driver Receiver Table 2 NOTI FIRE NET Connections HS NC...

Page 11: ...may be necessary to change the port designation for the wire connection on the HS NCM WMF WSF To change the wire port designation the HS NCM parameters must be changed via VeriFire Tools For instruct...

Page 12: ...4 8 m Genesis 4631 18 AWG 3 000 ft 914 4 m Belden 5320UJ 18 AWG 3 000 ft 914 4 m Genesis 4633 14 AWG 3 000 ft 914 4 m Belden 5320UM 18 AWG 3 000 ft 914 4 m Genesis 5502 16 AWG 1 000 ft 304 8 m Comtran...

Page 13: ...g and system connection Refer to Table 5 for a list of diagnostic indicators and their descriptions Refer to Figure 11 for diagnostic indicator locations HS NCM LEDS wmf Figure 11 Diagnostic Indicator...

Page 14: ...eceive Green Blinks On when data is received If not periodically blinking check the NUP cable for connection and integrity NUPB TX NUPB Transmit Green Blinks On when data is transmitted If not periodi...

Page 15: ...20 Installation Operations Programming 52745 52747 52746 NFS2 3030 Installation Operations Programming 52544 52545 52546 NFS 640 Installation Operations Programming 51332 51334 51333 NFS 3030 Installa...