HS-NCM Installation Document —

 P/N 54014:B2  04/25/2014

6.5  Approved Cables and Distances for HS-NCM Applications

The following table shows approved wiring cables that can be used with the HS-NCM and the maximum total distance 
allowed for each. 

6.6  External Power for HS-NCM Applications

When using the HS-NCM with UL 8th edition panels, UL 9th edition panels where power 
can not be applied via the NUP port or when configured as a repeater, a 24 VDC external 
power source is required. Where applicable, the external 24 VDC external power source 
must share the same ground reference as the NUP port.

Wire Type / Gauge

Maximum Distance:

Wire Type / Guage

Maximum Distance

Aerospace 7131KK / 16 AWG 

2000 ft. (609.6 m.)

Genesis 4433 / 14 AWG

3,000 ft. (914.4 m)

Belden 5220UM / 16 AWG

1,000 ft. (304.8 m)

Genesis 4631 / 18 AWG

3,000 ft. (914.4 m)

Belden 5320UJ / 18 AWG

3,000 ft. (914.4 m)

Genesis 4633 / 14 AWG

3,000 ft. (914.4 m)

Belden 5320UM / 18 AWG

3,000 ft. (914.4 m)

Genesis 5502 / 16 AWG

1,000 ft. (304.8 m)

Comtran 8696 / 18 AWG

1,000 ft. (304.8 m)

Lake Cable SNY141PR-NOT / 14 AWG

1,200 ft (365.8 m)

Comtran 8698 / 14 AWG

1,000 ft. (304.8 m)

Pyrotenax 2/16-246T / 16 AWG

425 ft (129.5 m)

Comtran 8706 / 16 AWG

1,000 ft. (304.8 m)

Radix CI14A0702-0000-I5000 / 14 AWG

1,500 ft (457.2 m)

Comtran 8709 / 14 AWG

1,000 ft. (304.8 m)

Radix CI16A0102-0000-I5000 / 16 AWG

1,600 ft (487.6 m)

Comtran 35777 VitaLink 2C/16 / 16 AWG

850 ft (259.0 m)

Shawflex 64220M140118700 / 14 AWG

250 ft (76.2 m)

Draka USA C FLPR-2C/16NS / 16 AWG

1,000 ft. (304.8 m)

West Penn AQ225 / 16 AWG

1,000 ft (304.8 m)

Genesis 4050 / 18 AWG

3,000 ft. (914.4 m)

West Penn D980 / 18 AWG

2,000 ft (609.6 m)

Genesis 4431 / 18 AWG

2,000 ft. (609.6 m)

West Penn D990 / 16 AWG

2,000 ft (609.6 m)

Table 4  Maximum Distance for Approved Cables.

– 24 VDC Out
+ 24 VDC Out
– 24 VDC In
+ 24 VDC In

TB1

HS-NCM

Summary of Contents for HS-NCM

Page 1: ...and assembly name can be found on the fire panel s circuit board NUP Port connections are still required for communication between the HS NCM and the fire panel One HS NCM can provide network communic...

Page 2: ...p to two fire alarm control panels and a programming computer Enables software and database upload download over High Speed Noti Fire Net Communication Circuit Voltage and Current Rating Protocol TB4...

Page 3: ...5 dB limit 9 125 micrometers single mode 30 dB limit Wavelength 1 1310 nanometers Fiber Connectors LC style Data is regenerated at each node Two network ports to allow simultaneous connection of up t...

Page 4: ...terminal wiring with strain relief Data is regenerated at each node Two network ports to allow simultaneous connection of up to two fire alarm control panels and a programming computer Enables softwa...

Page 5: ...wer source 2 Connect VeriFire Tools to the network or directly connected to the HS NCM 3 In VeriFire Tools access the Upload Download Screen 4 In the Network Node Session of the Upload Download screen...

Page 6: ...Installation Document P N 54014 B2 04 25 2014 7 Select HS NCM Parameters 8 The HS NCM Parameters screen will be displayed listing HS NCM defaults HS NCM context menu jpg HS NCM UPDL jpg HSNCMPARMSFOR...

Page 7: ...on code for the HS NCM Not user modifiable Port A Mode For HS NCM MF HS NCM SF and HS NCM MFSF Port A Mode is not applicable for Fiber ports Port A Mode will automatically be configured as Fiber and c...

Page 8: ...M MFSF CHS 4L 4N CHS2 M3 CHS M3 the NFS2 640 chassis or NFS 320 enclosure Mount the HS NCM in standard option module positions as described in your control panel installation manual Figure 4 shows CHS...

Page 9: ...egarding these devices refer to the documentation listed in Table 6 Supplemental Documentation NOTE The module cannot be mounted in the ADP 4B Dress Panel when a front slot of the CHS 4 or CHS 4N is o...

Page 10: ...h the HS NCM TB4 1 CH A Channel A Driver Receiver TB4 2 CH A Channel A Driver Receiver TB5 1 CH B Channel B Driver Receiver TB5 2 CH B Channel B Driver Receiver Table 2 NOTI FIRE NET Connections HS NC...

Page 11: ...may be necessary to change the port designation for the wire connection on the HS NCM WMF WSF To change the wire port designation the HS NCM parameters must be changed via VeriFire Tools For instruct...

Page 12: ...4 8 m Genesis 4631 18 AWG 3 000 ft 914 4 m Belden 5320UJ 18 AWG 3 000 ft 914 4 m Genesis 4633 14 AWG 3 000 ft 914 4 m Belden 5320UM 18 AWG 3 000 ft 914 4 m Genesis 5502 16 AWG 1 000 ft 304 8 m Comtran...

Page 13: ...g and system connection Refer to Table 5 for a list of diagnostic indicators and their descriptions Refer to Figure 11 for diagnostic indicator locations HS NCM LEDS wmf Figure 11 Diagnostic Indicator...

Page 14: ...eceive Green Blinks On when data is received If not periodically blinking check the NUP cable for connection and integrity NUPB TX NUPB Transmit Green Blinks On when data is transmitted If not periodi...

Page 15: ...20 Installation Operations Programming 52745 52747 52746 NFS2 3030 Installation Operations Programming 52544 52545 52546 NFS 640 Installation Operations Programming 51332 51334 51333 NFS 3030 Installa...

Reviews: