HS-NCM Installation Document —

 P/N 54014:B2  04/25/2014

6  Installation

6.1  Mounting Options

The HS-NCM is designed to mount in a variety of CAB-3/CAB-4 compatible chassis, in the NFS-320 enclosure, on a 
BMP-1 blank plate for dress panel mounting, or behind the DVC-EM in the CA-1 or CA-2 audio chassis. HS-NCM-W 
can be door-mounted; HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF, HS-NCM-WSF, or HS-NCM-MFSF must be 
installed in a stationary location. Recommended location is in the top row under the backbox’s knockout, so as to avoid 
over-bending fiber-optic cable. Avoid mounting other option boards in front of HS-NCM so that its LEDs are visible. 
Attach the HS-NCM using the four screws that ship with it.

Cabinet-mounting HS-NCM-W/HS-NCM-MF/HS-NCM-SF/HS-NCM-WMF/HS-NCM-WSF/HS-NCM-MFSF: 

CHS-4L/4N, CHS2-M3, CHS-M3, the NFS2-640 chassis or NFS-320 enclosure: Mount the HS-NCM in standard 
option module positions as described in your control panel installation manual. Figure 4 shows CHS-4L as an 
example.

CA-1, CA-2: Mount the HS-NCM-W/MF/SF behind a DVC-EM in either the CA-1 or CA-2 audio chassis. Figure 5 
illustrates how to install it in a CA-1. Mounting is the same behind a DVC-EM in the lower half-chassis of a CA-2. 

Door-mounting HS-NCM-W:

Door-mount on the ADP-4B Dress Panel on a single-space blank plate (BMP-1) for mounting in a CAB-4 series 
backbox, as described in Figure 6. 

Figure 4  Mounting HS-NCM in a Chassis (CHS-4L Shown)

NOTE: When mounting wire or fiber versions of the HS-NCM using the CHS-RL-MP chassis, refer to the 

CHS-RL-MP Product Installation Document

.

nf

s64

0

-m

nt

icm.cdr

Insert tab of option board into slot 

of chassis, and lay the HS-NCM 

board back against standoffs.

Slots

One HS-NCM board 

in CHS-4L

Two HS-NCM boards 

in CHS-4L

Summary of Contents for HS-NCM

Page 1: ...and assembly name can be found on the fire panel s circuit board NUP Port connections are still required for communication between the HS NCM and the fire panel One HS NCM can provide network communic...

Page 2: ...p to two fire alarm control panels and a programming computer Enables software and database upload download over High Speed Noti Fire Net Communication Circuit Voltage and Current Rating Protocol TB4...

Page 3: ...5 dB limit 9 125 micrometers single mode 30 dB limit Wavelength 1 1310 nanometers Fiber Connectors LC style Data is regenerated at each node Two network ports to allow simultaneous connection of up t...

Page 4: ...terminal wiring with strain relief Data is regenerated at each node Two network ports to allow simultaneous connection of up to two fire alarm control panels and a programming computer Enables softwa...

Page 5: ...wer source 2 Connect VeriFire Tools to the network or directly connected to the HS NCM 3 In VeriFire Tools access the Upload Download Screen 4 In the Network Node Session of the Upload Download screen...

Page 6: ...Installation Document P N 54014 B2 04 25 2014 7 Select HS NCM Parameters 8 The HS NCM Parameters screen will be displayed listing HS NCM defaults HS NCM context menu jpg HS NCM UPDL jpg HSNCMPARMSFOR...

Page 7: ...on code for the HS NCM Not user modifiable Port A Mode For HS NCM MF HS NCM SF and HS NCM MFSF Port A Mode is not applicable for Fiber ports Port A Mode will automatically be configured as Fiber and c...

Page 8: ...M MFSF CHS 4L 4N CHS2 M3 CHS M3 the NFS2 640 chassis or NFS 320 enclosure Mount the HS NCM in standard option module positions as described in your control panel installation manual Figure 4 shows CHS...

Page 9: ...egarding these devices refer to the documentation listed in Table 6 Supplemental Documentation NOTE The module cannot be mounted in the ADP 4B Dress Panel when a front slot of the CHS 4 or CHS 4N is o...

Page 10: ...h the HS NCM TB4 1 CH A Channel A Driver Receiver TB4 2 CH A Channel A Driver Receiver TB5 1 CH B Channel B Driver Receiver TB5 2 CH B Channel B Driver Receiver Table 2 NOTI FIRE NET Connections HS NC...

Page 11: ...may be necessary to change the port designation for the wire connection on the HS NCM WMF WSF To change the wire port designation the HS NCM parameters must be changed via VeriFire Tools For instruct...

Page 12: ...4 8 m Genesis 4631 18 AWG 3 000 ft 914 4 m Belden 5320UJ 18 AWG 3 000 ft 914 4 m Genesis 4633 14 AWG 3 000 ft 914 4 m Belden 5320UM 18 AWG 3 000 ft 914 4 m Genesis 5502 16 AWG 1 000 ft 304 8 m Comtran...

Page 13: ...g and system connection Refer to Table 5 for a list of diagnostic indicators and their descriptions Refer to Figure 11 for diagnostic indicator locations HS NCM LEDS wmf Figure 11 Diagnostic Indicator...

Page 14: ...eceive Green Blinks On when data is received If not periodically blinking check the NUP cable for connection and integrity NUPB TX NUPB Transmit Green Blinks On when data is transmitted If not periodi...

Page 15: ...20 Installation Operations Programming 52745 52747 52746 NFS2 3030 Installation Operations Programming 52544 52545 52546 NFS 640 Installation Operations Programming 51332 51334 51333 NFS 3030 Installa...