HS-NCM Installation Document —
P/N 54014:B2 04/25/2014
11
6.3 Interconnecting the HS-NCM-MF/SF/WMF/WSF/MFSF
An HS-NCM-MF/SF/MFSF may be connected to any of the following devices:
•
HS-NCM-MF/SF/WMF/WSF/MFSF (in another panel)
•
ONYXWORKS-HNMF/SF
For information regarding these devices, refer to the documentation listed in Table 6 “Supplemental Documentation”.
Figure 9 HS-NCM-MF/SF/MFSF Connection
6.4 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable—use a HS-NCM-WMF or HS-
NCM-WSF as an interface between wire and fiber.
Fiber ports are not polarity sensitive. However, port-to-port wiring for the HS-NCM wire connections are polarity
sensitive. When converting from a wire to fiber network, it may be necessary to change the port designation for the wire
connection on the HS-NCM-WMF/WSF. To change the wire port designation, the HS-NCM parameters must be changed
via VeriFire Tools. For instructions on how to change the HS-NCM parameters, refer to “HS-NCM Configuration” on
page 5.
Figure 10 Wire-to-Fiber Connections
See Section 3, “The Network Communications Module for Fiber (HS-NCM-MF, HS-NCM-SF, HS-NCM-MFSF)” for
requirements and restrictions on the use of fiber-optic cable. See the High-Speed Noti•Fire•Net™ Manual
for a discussion
of all compatible configurations.
U34
CH A
Transmit
U34
CH A
Receive
U35
CH B
Transmit
U35
CH B
Receive
Table 3 NOTI•FIRE•NET™ Connections: HS-NCM-MF/SF/MFSF
HS
-NCM
-f-co
nn
ex.wm
f
From previous
node, Port B
To next node,
Port A
U35
Channel B
U35
Channel B
U34
Channel A
U34
Channel A
From
Previous
HS-NCM-W
To Next
HS-NCM-MF/SF
HS-NCM-W
HS-NCM-WMF/WSF
HS-NCM-MF/SF/MFSF
U9
Channel B
U8
Channel A
U9
Channel B
U8
Channel A