54
AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
Software Type ID Codes
Alphabetical List
MAN REL DELAY
Monitor module that provides manual release with a 10 second delay for a releasing zone through connection
to a pull station
MCP
Manual fire-alarm-activating device.
MONITOR
Alarm-monitoring device
MNS CONTROL
Activates control module mass notification devices when an MNS event occurs
MNS GENERAL
Activates NAC mass notification devices when an MNS event occurs
MNS RELAY
Activates relay mass notification devices when an MNS event occurs
MNS SPEAKER
Activates speaker mass notification devices when an MNS event occurs
MNS STROBE
Activates strobe mass notification devices when an MNS event occurs
NAC
Supervised NAC for notification appliance.
NON (DUCTP)
Non-latching duct detector.
NON FIRE
Monitors non fire activations
NONRESET CTL
Output unaffected by “System Reset” command
P/CO (C SUP)
For use with a Photo/CO detector. If the CO element in the detector activates, a supervisory condition is
generated on the fire panel. An activation via the heat or photo element of the Photo/CO detector will generate
an alarm condition on the panel.
P/CO (P SUP)
For use with a Photo/CO detector. If the photo element in the detector activates, a supervisory condition is
generated on the fire panel. An activation via the CO or heat element of the Photo/CO detector will generate
an alarm condition on the panel.
PHOTO/CO
For use with a Photo/CO detector. Activation of the CO, photo or heat elements will generate an alarm
condition on the fire panel.
POWER MONITR
Monitor for main and auxiliary power supplies
PROCESS AUTO
Indicates process condition, tracking
PROCESS MON
Indicates process condition, latching
PULL STATION
Manual fire-alarm activating device
REL AUDIBLE
Activates audio or visual devices steady when releasing starts
REL END BELL
Control module used to activate NAC audio or visual device when releasing circuits shut off
RELAY
Form-C relay control module
REL. FORM C
Form-C relay that directs outputs to perform a releasing function
RELEASE CKT
Directs outputs to perform a releasing function
RESET SWITCH
Monitor used to reset the control panel
SECOND SHOT
Monitor module that provides a second manual release for a releasing zone through connection to a pull
station
SIL SWITCH
Monitor used as Signal Silence switch, turning off all activated silenceable outputs
SMOKE ACCLIM
Combination photoelectric/heat detector
SMOKE()
Combination photoelectric/heat detector with low temperature warning
SMOKE CONVEN
Conventional smoke detector attached to an FZM-1
SMOKE(DUCTL)
Duct laser smoke detector
SMOKE(DUCTP)
Duct photoelectric smoke detector
SMOKE(HARSH)
HARSH smoke detector
SMOKE(ION)
Ionization smoke detector
SMOKE(LASER)
Laser smoke detector
SMOKE(PHOTO)
Photoelectric smoke detector
SPEAKER
Control module for speaker
SPRINKLR SYS
Monitor for a waterflow device
SUP L(DUCTL)
Duct laser smoke detector, latching
SUP L(DUCTP)
Photoelectric smoke detector used as a duct detector to report supervisory condition rather than alarm,
latching
SUP L(LASER)
Laser smoke detector, latching
SUP L(PHOTO)
Photoelectric smoke detector, latching
SUP T(DUCTL)
Duct laser smoke detector, tracking
SUP T(DUCTP)
Photoelectric smoke detector used as a duct detector to report supervisory condition rather than alarm,
tracking
SUP T(LASER)
Laser smoke detector, tracking
SUP T(PHOTO)
Photoelectric smoke detector, tracking
TAMPER
Monitor for activation of tamper switch
Software Type ID Code
Device