AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
11
Message Formats
General Information
The top four lines contain event information, and are formatted as follows:
The system fault event example screen below shows an annunciator fault condition.
Figure 1.4 System Event Display Example
The event counts display shows the counts for outstanding events. The date in line eight gives the current time. The soft keys may be
used to deal with the event; their functions are described in the Operation section of this manual.
Mass Notification Events
When a local mass notification event occurs on the fire panel, a message is generated to the panel that displays on the top of the LCD
screen, and soft keys display available functions that may be used to handle the event.
The format of the first line will vary slightly as follows, depending on the type of event.:
F A U L T
A N N U N 1 F A U L T
L A K E V I E W G E N E R A L H O S P I T A L
1 1 : 5 8 : 4 5 A T U E J A N 2 2 , 2 0 1 9
Line 1 - Displays
FAULT and whether it
has been
acknowledged or
Line 2 - Displays fault
type
Line 3 - Displays custom
message.
Line 4 - Displays event
time and date and node
address.
F A U L T : 1 O F 2
F A U L T
A N N U N 1 F A U L T
1 1 : 5 8 : 4 3 A M O N 2 1 , J A N , 2 0 1 9
2
F L T A N N U N 1 N O A N S W E R
A L M : 0
S U P : 0
F L T : 2
D I S : 0
O T H E R : 0
1 1 : 5 8 : 4 3 A M O N 2 1 , J A N , 2 0 1 9
M N A L A R M
S E C U R I T Y O F F I C E
M A I N B L D G
F I R S T F L O O R
Z F 2 0
M N M O N
1 1 : 5 8 : 4 5 A T U E J A N 2 2 , 2 0 1 3
L 0 3 M 0 0 2
Line 1
Displays the type of
event, and whether
it has been
acknowledged or
cleared.
M N F A U L T
D E T E C T O R F A I L E D T E S T
S E C U R I T Y O F F I C E
M A I N B L D G
F I R S T F L O O R
Z F 2 2
M N M O N
1 1 : 5 8 : 4 5 A T U E J A N 2 2 , 2 0 1 3
L 0 3 M 0 0 3
Line 1
Displays
MN FAULT, and
whether it has been
acknowledged or
cleared.
Event
Format (not
fault or
supervisory)
Event
Format
(fault)
Line 1
Displays
MN SUPERVISORY
and whether it has
been acknowledged
or cleared.
M N S U P E R V I S O R Y
S E C U R I T Y O F F I C E
M A I N B L D G
F I R S T F L O O R
Z F 2 1
M N S U P L
1 1 : 5 8 : 4 5 A T U E J A N 2 2 , 2 0 1 3
L 0 3 M 0 0 4
Event
Format
(supervisory)