OM-NI 2/20
11
The pump and strainer should accessible for maintenance
and service, not in a location where they can be stepped
on or damaged.
Install isolation valves so that the pump and strainer can
be maintained or serviced.
There are only two mounting positions for the pump
installation. Position “A” is the preferred mounting
(Figure 8, below).
Installation
Fig. 9: Hose stretching
Fig. 8: Pump installation
When connecting fittings to the pump inlet and outlet use
Teflon tape or other type of pipe sealant.
Hand tight is sufficient,
DO NOT OVER-TIGHTEN.
Using excessive force can split or break off the pump
head. The weight of the water in the pump outlet hose,
combined with the weight of the hose, can stress the pump
outlet connection. Any type of impact on the hose can also
stress the connection. Support the hose within 18” (46cm)
of the pump outlet.
Insulate the ice delivery hose with a minimum of ½” thick
insulation. Secure the hose on the auger outlet with a
constant torque hose clamp. Connect the outlet of the hose
to the ice bin using a bulkhead fitting to prevent restric
-
tion at the outlet. Secure the hose at the bulkhead fitting to
prevent it from pulling out.
If you have difficulty getting the ice delivery hose onto
the auger outlet, heat the hose and stretch it out using slip-
lock pliers. To heat the hose immerse in hot water or use a
heat-shrink gun. Burn hazard use caution and wear safety
gear. Additionally, spraying the auger outlet and inside of
the hose with 409® cleaner to lubricate it.
POSITION (A)
POSITION (B)