background image

34 

 

Annex 1 

Characteristic of temp. sensor 

Temp.

 

 

Resistance KΩ 

 

 

  Temp.

 

 

Resistance KΩ 

 

 

  Temp.

 

 

Resistance KΩ 

-10 

62.2756 

 

 

17 

14.6181 

 

 

44 

4.3874 

-9 

58.7079 

 

 

18 

13.918 

 

 

45 

4.2126 

-8 

56.3694 

 

 

19 

13.2631 

 

 

46 

4.0459 

-7 

52.2438 

 

 

20 

12.6431 

 

 

47 

3.8867 

-6 

49.3161 

 

 

21 

12.0561 

 

 

48 

3.7348 

-5 

46.5725 

 

 

22 

11.5 

 

 

49 

3.5896 

-4 

44 

 

 

23 

10.9731 

 

 

50 

3.451 

-3 

41.5878 

 

 

24 

10.4736 

 

 

51 

3.3185 

-2 

39.8239 

 

 

25 

10 

 

 

52 

3.1918 

-1 

37.1988 

 

 

26 

9.5507 

 

 

53 

3.0707 

35.2024 

 

 

27 

9.1245 

 

 

54 

2.959 

33.3269 

 

 

28 

8.7198 

 

 

55 

2.8442 

31.5635 

 

 

29 

8.3357 

 

 

56 

2.7382 

29.9058 

 

 

30 

7.9708 

 

 

57 

2.6368 

28.3459 

 

 

31 

7.6241 

 

 

58 

2.5397 

26.8778 

 

 

32 

7.2946 

 

 

59 

2.4468 

25.4954 

 

 

33 

6.9814 

 

 

60 

2.3577 

24.1932 

 

 

34 

6.6835 

 

 

61 

2.2725 

22.5662 

 

 

35 

6.4002 

 

 

62 

2.1907 

21.8094 

 

 

36 

6.1306 

 

 

63 

2.1124 

10 

20.7184 

 

 

37 

5.8736 

 

 

64 

2.0373 

11 

19.6891 

 

 

38 

5.6296 

 

 

65 

1.9653 

12 

18.7177 

 

 

39 

5.3969 

 

 

66 

1.8963 

13 

17.8005 

 

 

40 

5.1752 

 

 

67 

1.830 

14 

16.9341 

 

 

41 

4.9639 

 

 

68 

1.7665 

15 

16.1156 

 

 

42 

4.7625 

 

 

69 

1.7055 

16 

15.3418 

 

 

43 

4.5705 

 

 

70 

1.6469 

 

Summary of Contents for M2OC-18HRDN1-M

Page 1: ...RODUCTS LTD Tel 604 4308496 Fax 1 866 9034371 www northamericanhvac com Service Manual DC Inverter Multi Zone Split Wall Mounted Type Indoor Models MSV1I 09HRDN1 M MSV1I 12HRDN1 M Outdoor Models M2OC 18HRDN1 M M3OC 27HRDN1 M ...

Page 2: ...Product features 2 Dimensions 3 Refrigeration cycle diagram 4 Operation limits 5 Indoor unit combination 6 Wiring diagram 7 Electric control functions 8 Troubleshooting Annex 1 Characteristic of temp sensor Annex 2 Reference data ...

Page 3: ... The unit will decide the louver direction according to operation mode high med low breeze Restarting is for approx 3 minutes Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooling mode Room temperature sensor Pipe temperature sensor Indoor unit Operation by remote controller Sensing by room temperature Room temperature control Anti freezing control in c...

Page 4: ...iency at operation mode Hydrophilic aluminum fin It is only operated in the heating operation mode except defrosting operation Anti rust cabinet Valve protection cover 4 way valve control Made from electrolytic zinc steel sheet and anti rust coated components Low noise air flow system Bird tail propeller fan makes the outdoor unit run more quietly Discharge pipe temperature protect Driving heating...

Page 5: ...5 2 Dimensions 2 1 Vertu Series Indoor unit 9K 12K 2 2 Outdoor unit a M2OC 18HRDN1 M M3OC 27HRDN1 M Dimension Mode W H D 9K 795 270 165 12K 845 286 165 ...

Page 6: ...6 b M4OC 36HRDN1 M ...

Page 7: ...7 3 Refrigeration Cycle Diagram 3 1 Refrigeration circuit drawing of inverter quadplex type 3 2 Refrigeration circuit drawing of inverter trinary type ...

Page 8: ...peration range Cooling mode Indoor temperature 17 Outdoor temperature 0 50 Heating mode Indoor temperature 30 Outdoor temperature 15 24 Dry mode Indoor temperature 10 Outdoor temperature 0 43 Liquid valve A Gas valve C EXV C 4 way valve Compressor Condenser Axial flow fan EXV B EXV A Gas valve A Gas valve B Liquid valve C Liquid valve B Evaporator Cross flow fan Indoor Unit Capillary A Capillary B...

Page 9: ...M3OC 27HRDN1 M One unit Two unit Three unit 9 9 9 9 12 9 9 9 9 9 12 12 12 12 5 3 Indoor unit combination for M4OC 36HRDN1 M One unit Two unit Three unit Four unit 9 9 9 9 12 9 9 9 9 9 12 9 9 9 9 9 9 9 12 9 9 12 12 12 12 12 9 12 12 12 12 12 Note As the capacity of exceeding the standard mix of red colors identify ways not recommended to use ...

Page 10: ...10 6 Wiring Diagram 6 1 Indoor unit 9k 12k ...

Page 11: ...11 6 2 Outdoor unit M2OC 18HRDN1 M 6 3 Outdoor unit M3OC 27HRDN1 M ...

Page 12: ...12 6 4 Outdoor unit M4OC 36HRDN1 M ...

Page 13: ... AIR indication lamp Lights up when CLEAN AIR feature is activated and Ionizer can generate abundant anions to fill the room with refreshing and natural air PRE DEF indicator This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating mode TURBO indication lamp Lights up when select TURBO function on cooling opera...

Page 14: ...switch in outdoor PCB Push the switch SW1 to check the states of unit when the unit is running The digital display tube will display the follow procedure when push SW1 each time Display Remark 1 Indoor unit capacity demand code 2 Outdoor unit running mode code Off 0 Cooling 1 Heating 2 3 Amendatory capacity demand code 4 Outdoor unit fan motor state Off 0 Low speed 1 High speed 2 5 Evaporator outl...

Page 15: ...y Number of indoor unit 1 1 2 2 3 3 7 4 4Outdoor ambient temp Display Corresponding temp Display Corresponding temp Display Corresponding temp 15 7 5 50 10 80 25 16 7 51 10 5 81 25 5 17 6 5 52 11 82 26 18 6 53 11 5 83 26 5 19 5 5 53 11 5 84 27 20 5 54 12 85 27 5 21 4 5 55 12 5 86 28 22 4 56 13 87 28 5 23 3 5 57 13 5 88 29 24 3 58 14 89 29 5 26 2 59 14 5 90 30 27 1 5 60 15 91 30 5 28 1 61 15 5 92 3...

Page 16: ...60 42 6 73 21 5 15 60 65 43 6 5 74 22 16 65 70 44 7 75 22 5 45 7 5 75 22 5 46 8 76 23 47 8 5 77 23 5 48 9 78 24 49 9 5 79 24 5 7 4 5Current of outdoor unit Display Corresponding mode 60 8 0A 65 8 5A 70 9 1A 75 9 6A 80 10 1A 85 10 7A 90 11 2A 100 12 3A 110 13 4A 120 14 5A 130 15 6A 140 16 7A 150 17 9A 200 24A 7 4 6 No 1 opening degree of electronic expansion valve Opening degree equals the display ...

Page 17: ... Indoor LED displays E2 and can t return to normal operation automatically 7 5 8 Current protection when the current is more than X A the compressor stops and Outdoor LED diaplays P3 for 30 seconds and the unit will restart after 3 minutes X is 12 5A for 18K 1x2 unit is 14 5A for 27K 1x3 unit and is 20A for 36K 1x4 unit 7 5 9 Outdoor condenser high temperature protection Under cooling mode if T3 6...

Page 18: ... of the indoor heat exchanger is the same as that of cooling mode 7 9Heating mode 7 9 1Indoor Fan actions at heating mode Indoor Fan can be set at HIGH MID LOW AUTO by using a remote controller but Anti cold wind function prevails Anti cold wind control function at heating mode Condition T Indoor exchanger temp Indoor fan speed Indoor exchanger temp up T 34 Off 34 T 37 Breeze 37 T 44 Low speed T 4...

Page 19: ...Outdoor fan switches off d Indoor fan running according to anti cold wind function in heating mode 7 11Automatic operation mode The air conditioner automatically selects one of the following operation modes cooling heating or fan only according to the temp difference between room temp TA and set temp TS The temp can be adjusted between 17 30 C by remote controller TA TS Operation mode TA TS 1 Cool...

Page 20: ...urs unit cancels this mode automatically and the unit turns off 7 14 6 Auto restart function In case of a sudden power failure this function automatically sets the unit to previous settings before the power failure when power returns 7 15 Mode conflict The indoor units can not work cooling mode and heating at same time Heating mode has a priority 7 15 1Definition Cooling mode Heating Mode Fan Off ...

Page 21: ...V The voltage in P6 in outdoor PCB is high voltage about 310V 8 2 Troubleshooting for indoor unit Display LED STATUS E0 EEPROM error E1 Communication error between indoor and outdoor unit E2 Zero crossing examination error E3 Fan speed beyond control E5 Outdoor units temp sensor or connector of temp sensor is defective E6 Indoor units temp sensor or connector of temp sensor is defective P0 Inverte...

Page 22: ...temp sensor is defective E5 Compressor volt protection E7 Communication error between outdoor IC and DSP P0 Compressor discharge temp protection P1 High pressure protection just for 36K 1x4 units P2 Low pressure protection just for 36K 1x4 units P3 Compressor current protection P4 Inverter module protection P5 Outdoor temp too low protection P6 Condenser high temperature protection P7 Compressor d...

Page 23: ...ower supply turn on the unit with remote controller Does the unit work normally Check the wiring between indoor and outdoor unit Is the connection of L N S and GND good Is the GND connection on outdoor PCB good NO NO Reconnect and retest again Is the LED4 red on outdoor PCB bright and LED1 yellow blinking Replace outdoor e box Yes Yes The power supply for outdoor PCB is fail Check the wiring on ou...

Page 24: ...e connector and reconnect Replace the sensor and check if E6 display again NO YES Replace the indoor PCB YES Is the outdoor temperature sensor connector and connection good Repair the connector and reconnect Replace the sensor and check if E5 display again NO YES Replace outdoor e box YES Is the indoor fan motor connector and connection good Repair the connector and reconnect Is voltage being appl...

Page 25: ...ing the units NO YES Replace the outdoor e box Revise the power and retest Is voltage normal NO YES Is all connection good NO Revise the power and retest YES Is the wiring to compressor right YES Check the moduler if some components blow out or be failure YES Repair or replace the moduler YES Is it breakdown between P N P V P W N V N W or V W of inverter moduler YES Replace the moduler YES Check t...

Page 26: ...nsor or connector of pipe temp sensor is defective Circuit or software error on indoor PCB Replace indoor PCB YES Does compressor operate Is the connection good Is refrigerant circulation volume normal NO NO Charge refrigerant Is abnormality the same after gas charging NO Check refrigerant system such as clogging of capillary etc Reconnect and retest NO YES Is protector normal Replace the protecto...

Page 27: ...r or connector of pipe temp sensor is Is connection to connector of pipe temp sensor good Check the resistance of the temp sensor according to Annex 1 Repair connector No Yes Replace the sensor Is connection to connector of pipe temp sensor good Check the resistance of the temp sensor according to Annex 1 Repair connector No Yes Replace the sensor Is connection to connector of pipe temp sensor goo...

Page 28: ...TUS E5 Compressor volt protection Yes Is connection to connector of pipe temp sensor good Check the resistance of the temp sensor according to Annex 1 Repair connector No Replace the sensor Is connection to connector of pipe temp sensor good Check the resistance of the temp sensor according to Annex 1 Repair connector No Yes Replace the sensor ...

Page 29: ...ge is about 220V turn off the power supply to indoor unit and turn it on again after 1 minute Does the trouble occur again Check the voltage of secondary of T3 transformer in outdoor power board is this voltage 12 14V AC No Replace the outdoor power board ...

Page 30: ...3 3v voltage in outdoor main board Power Board CN1 Purple wire and yellow GND Inverter module defective Rectifier circuit is bad connection or defective when the voltage in outdoor is abnormal D and N 310V DC No Yes No Yes Check the signal wires between outdoor PCBs is it connected good Check the IC6 IC7 at Outdoor power PCB Normally Input voltage 5V changeable Output voltage 5V changeable Outdoor...

Page 31: ...ssor drive malfunction drive protection arose Check the resistance of compressor normally U and V is 1 ohm U and W is 1 ohm V and W is 1ohm Turn one indoor unit only Does the compressor start after 3 minutes Does the trouble occur again after compressor running some time No Yes No The compressor is defective Check the refrigerant circulation volume and pressure No The compressor is defective Yes I...

Page 32: ...al Replace the outdoor power board If the problem comes to again check wingding resistance of inverter compressor is it right Replace inverter compressor Repair connector Yes No No Replace inverter compressor Repair connector If the problem comes to again check wingding resistance of inverter compressor is it 1 ohm Replace the outdoor power board Are the U V W connected to compressor and inverter ...

Page 33: ...or pipe temp is more than 65 C the unit will stop and unit runs again when outdoor pipe temp less than 52 C Is the outdoor pipe temp more than 65 C Is the outdoor pipe temp sensor right according to the annex 1 Replace the outdoor main board No Yes Replace the outdoor pipe temp sensor No ...

Page 34: ...52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26 8778 32 7 2946 59 2 4468 6 25 4954 33 6 9814 60 2 3577 7 24 1932 34 6 6835 61 2 2725 8 22 5662 35 6 4002 62 2 1907 9 21 8094 36 6 1306 63 2 1124 10 20 7184 37 5 8736 64 2 0373 11 19 6891 38 5 6296 65 1 9653...

Page 35: ...60 150V AC P N DC 310V c Photo couple PC817 PC851 Control side 5V AC side 24V AC d S terminal and N changeable from 0 24V 2 Check the Diode Bridge component In wiring diagram rectifier Remark If this part is abnormal the LED will not light Multi meter Result Forward Resistance Backward Resistance _ Infinite Infinite 500 ohm Infinite 500 ohm Infinite ...