33
Outdoor unit display
LED STATUS
P6
Condenser high-temperature protection
When outdoor pipe temp. is more than 65°C, the unit will stop, and unit runs again when outdoor
pipe temp. less than 52°C.
Is the outdoor pipe temp. more than 65°C ?
Is the outdoor pipe temp sensor right according to the annex 1
Replace the outdoor main board
No
Yes
Replace the outdoor pipe temp sensor
No