C
B
A
Figure I7: Actuator
Table I16: Outdoor Three-way Valve Dimensions
(10 to 21 tons)
Value Nominal Size
Dimensions (Inches [mm])
Inches
DN [mm]
A
B
C
1¼”
32 mm
3.96” [100.6] 2.21” [56.2]
2.14” [54.3]
1½”
40 mm
4.39” [111.6] 2.45” [62.2]
2.33” [59.1]
2”
50 mm
4.90” [124.5] 2.68” [68.0]
2.60” [66.0]
Table I17: Actuator Specifications
Torque
162 in-lbs [18 Nm]
Angle of rotation
95° (adjustable with mechanical stops)
Fits shaft diameter
9/16”...3/4”
Manual override
External push button
Direction of rotation
External switch
Dimensions
10.66” x 5.28” x 4.88”
[271 x 134 x 124 mm]
Electrical connection
Terminal strip
Overload connection
Electronic throughout rotation
Auxiliary switch(es)
Add on: 1 or 2 SPDT, 3A (0.5A inductive)
at 250V one switch adjustable 25° to 85°
Housing specifications
NEMA 4/4X, IP66/IP67
Agency listings
cULus according to UL 30730-1A/- 2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC
Control shaft length
Minimum ¾”
Maximum 2¼”
10.66”
1.52”
9.56”
1.10”
2.01”
5.28”
0.21”
5.52”
5.15”
4.41”
AM..N4 9/10”...3/4” 3/8”...9/10” 9/10”...3/4”
4.88”
Figure I6: Outdoor three-way valve actuator
(10 to 21 tons)
Table I15: Outdoor Three-way Valve Actuator
Technical and Dimensional Data (10 to 21 tons)
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption
Running
Holding
2.5 W
0.4 W
Transformer sizing
5 VA (Class 2 power source)
Electrical connection
Screw terminal (for 26–14 GA wire) ½”
conduit connector
Overload protection
Electronic throughout 0° to 95° rotation
Operating range Y
2–10 VDC, 4–20 mA
Feedback output U
1–10 VDC, max. 0.5 mA
Input impedance
100 Ω [0.1 mA], 500 Ω
Angle of rotation
Max 95° adjustable with mechanical stop
Torque
160 in-lb [16 Nm]
Direction of rotation
Reversible with switch
Position indication
Pointer
Manual override
External push button
Running time
95 seconds constant independent of load
Humidity
5% to 95% RH non-condensing
(EN 60730-1)
Ambient temperature
−22°F to 122°F [−30°C to 50°C]
Storage temperature
−40°F to 176°F [−40°C to 80°C]
Housing IP66/67
UL Type 4X, NEMA 4X
Housing material
UL94-5VA
Agency listings†
cULus acc. to UL60730-1A/-2- 14,CAN/
CSA E60730-1, CSA C22.2 No. 24-93,
CE acc. to 89/336/EEC
Noise level
<45 db (A)
Servicing
Maintenance free
Quality standard
ISO 9001
Weight
3.3 lbs [1.5 kg]