Table I3: Two-way Water Shut-off Valve Sizing and Technical Data
Circuit
Number
Tons
Minimum
US GPM
2
Condenser Pressure
Drop (PSI)
1
Condenser
Maximum
Pressure (PSI)
Two-way Water Shut-off Valve*
Indoor PN
Outdoor PN Cv1
Maximum
Pressure (PSI)*
Size
FPT
Single
circuit
2
6
4.4
400
500016467S 500027835
14
600
¾
3
9
4.5
400
500016467S 500027835
14
600
¾
4
12
3.2
400
500016467S 500027835
14
600
¾
5
15
5.7
400
500016467S 500027835
14
600
¾
6
18
7.6
400
500016468S 500027836
19
600
1¼
8
22
3.5
400
500016468S 500027836
19
600
1¼
10
30
5.7
400
500016468S 500027836
19
400
1¼
12
36
8.7
400
201909070S 500027838
37
400
1½
14
42
7.3
400
201909070S 500027838
37
400
1½
16
44
3.8
400
201909070S 500027838
37
400
1½
Dual
circuit
6
18
4.7
400
500016468S 500027838
19
600
1¼
8
22
3.5
400
500016468S 500027836
19
600
1¼
10
30
5.7
400
500016468S 500027836
19
600
1¼
12
36
8.7
400
201909070S 500027836
37
400
1½
14
35
4.2
350
201909070S 500027838
37
400
1½
16
40
5.4
350
201909070S 500027838
37
400
1½
21
53
5.2
350
500016469S 500027839
57
400
2
* Two-way water shut-off valve is to turn water flow on or off to the unit.
Maximum close off pressure 200 psi.
1 – Values are based on water.
2 – Please refer to Venmar Select™ Web Edition for minimum and maximum GPM values.
VCES-VHC-IOM-1F – VHC-36, -42 & -50