Page 34 RHC 8000 EN April 2019 D301207 Issue C
9. Parts Listing
Description
Type
Part Number
Application
Settings
Differential pres-
sure switch S3
30-60621-150
8045 09
155Pa
off
30-60617-135
8060 12
135Pa
off
30-60617-150
8075 09
150Pa
off
30-60621-130
8075 15
135Pa
off
30-60617-120
8100 12
120Pa
off
30-60617-290
8125M 15
290Pa
off
30-60617-220
8150M 18
220Pa
off
start
30-60617-75
8175M 21
75Pa
on
run
30-60617-155
8175M 21
155Pa
off
30-60617-180
8200M 24
180Pa
off
Thermal overheat
control (limit) LC1
T.O.D. 60T
11 201614
03-400US-01
All
76°C out
54°C in
Thermal overheat
control (limit) LC3
IMT 151
03-24959
All
96°C out
reset
Combustion fan
M3 (RHC 8000
mod)
Aa-
co.602.75M
36-79094-13
8045-8100
20-60 sec 60-120sec
Combustion fan
M3 (RHC 8000M
mod)
EBM
G2E160
AL19 56
20-25745
8125M-8175M 20-60 sec 60-120sec
Combustion fan
M3 (RHC 8200M
mod)
Airflow
BWTLG0
8200M
Modulating valve
Honeywell
VR46 with
modureg
All
Fan delay control
(K 1.1) FCR
T.O.D 12
S 20 LX-
2578A
03-25167
20-60 sec 60-120sec
X-Baffle assembly
45mm
1001978
All
Burner head
Inshot
1002831
All
Ignition Controller
Brahma
03-25322
All
Ignition electrode
ER
Channel
products
03-400US-42
All
Flame sensor
Channel
products
SC543
All
Filter
2.0A
30-617747
All
Summary of Contents for Reznor RHC DJL 8000