Page 16 RHC 8000 EN April 2019 D301207 Issue C
To facilitate servicing, the air heater must be
fitted with an approved gas service tap and
union fitting or union tap adjacent to the
appliance.
The inlet gas supply line must be installed so
as to permit the access door to be opened
and to allow removal of slide out burner
assembly.
Check that the gas category is in
accordance with the data described on the
air heater.
An adequate gas supply sized to provide the
dynamic pressure for the volume required
for the air heater(s) is essential to maintain
the nominal heat input.
Account of other gas fired plant using the
same gas service must also be taken into
account.
A 90° action, positive stopped gas
service tap must be fitted adjacent to the
appliance, fitted in a manner to facilitate
appliance burner removal for service
purposes, see figure 7.
Ensure that the gas service includes a
filter and has been tested and purged in
accordance with prescribed practice prior
to commissioning and taking the appliance
into service.
As a rule, gas service pipes should not be
routed through air ducts. Should it be
necessary to do so then pipe work joints
must not be made within the air duct
4. Installation
4.1 Unpacking and Preparation
Prior to dispatch, the air heater was
operated and tested at the factory.
Check the shipping label and data plate to
ensure the specification of gas and electrical
supplies are compatible.
Read this document and become familiar
with the installation requirements and the
appliance before commencing installation.
4.2 Fitting the Flue System
Flue pipe runs may be horizontal or vertical
and terminate either through the wall or
roof. See table 12 for maximum vent length
for an appliance installed as type B
4.2.1 Fitting the Flue Pipe
Flue pipes must be sealed. Use seamless,
aluminum or stainless steel pipe. Follow
pipe manufacturer’s instructions
4.2.2 Installing a Grille
On the combustion air inlet pipe for power
vent (Type B installations)
When installed as a type B appliance,
protect the inlet by fitting an access grille
on the socket.
Figure 7 gas connection detail Rc 3/4
(8000 models) or Rc 11/4 (8000M models)