Page 20 RHC 8000 EN April 2019 D301207 Issue C
5.5.1 Burner Gas Pressure
Adjustment
RHC 8000
8045 09
8060 12
8075 09
8075 15
8100 12
8125M 15
8150M 18
8175M 21
8200M 24
Bur
ner
pr
essur
e at
100%
G20
mbar
6.9
6.9
6.9
6.8
6.9
7.1
7.3
7.7
7.7
G25
mbar
10.3
10.2
10.2
10.2
10.2
N/A
N/A
N/A
12.2
G25.3
mbar
10.3
10.2
10.2
10.2
10.2
N/A
N/A
N/A
12.0
Bur
ner
pr
essur
e at
50%
G20
mbar
1.9
1.9
2.0
1.8
2.1
1.9
2.0
2.1
2.2
G25
mbar
2.6
2.8
2.7
2.5
3.1
N/A
N/A
N/A
3.3
G25.3
mbar
2.6
2.8
2.7
2.5
3.0
N/A
N/A
N/A
3.1
Gas
consumption
at 50%
G20
m3/h
2.7
3.6
4.4
4.4
5.7
7.3
8.7
10.1
11.7
G25
/
G25.3
m3/h
3.1
4.1
5.1
5.1
6.7
8.5
10.2
11.8
13.6
Table 14 – gas pr
essur
es and low rate consumption values
Summary of Contents for Reznor RHC DJL 8000