Page 12 RHC 8000 EN April 2019 D301207 Issue C
• the temperature rise of the air through the enclosure (around the tubes)
• the inlet air temperature passing over the heat exchanger.
In function of the expected minimum inlet air temperature, the minimum required
temperature rise (to avoid condensation) must be derived from the chart below).
Type
H
H1
Y
Y2
W
W1
E
8045 09
741
671
1244
1170
400
400
400
8060 12
950
880
1244
1170
400
400
400
8075 09
741
671
1844
1770
400
400
400
8075 15
1160
1070
1244
1170
400
400
400
8100 12
950
880
1844
1170
400
400
400
8125M 15
1272
1202
1844
1770
400
460
420
8150M 18
1481
1411
1844
1770
400
460
420
8175M 21
1691
1621
1844
1770
400
460
420
8200M 24
1900
1830
1846
1770
530
530
470
Example :
• expected minimum inlet temperature = -5°C
• minimum required temperature rise shown on the chart = +13°K
Table 1 indicates the heat output (kW) of the different models.
The maximum allowable airflow through the enclosure (duct channel) around the tubes can
be calculated as follows
Example 1: Tmin = 13K (with minimum inlet temperature = -5°C)
model 8100 12 at 100% heat output : 99.94kW results into Vmax = 22459m³/h
Example 2: Tmin = 13K (with minimum inlet temperature = -5°C)
model 8100 12 at 50% modulation (see table 1 ‘heat output’) : 47.48kW results into :
Remark For air heaters with modulating gas valve attention must be given to determine
the maximum allowable airflow in function of the appropriate heat input
Table 8 Duct channel & controls compartment
Summary of Contents for Reznor RHC DJL 8000
Page 2: ......
Page 41: ...RHC 8000 EN April 2019 D301207 Issue C Page 39...