background image

6

units and apply the black neoprene gasket tape to the top of 
the coil case (except the rear surface). Make sure there are 
no gaps on the front and side flanges.

2. Carefully place the modular air handler on top of the cased 

coil making sure not to damage the cased coil flanges. The 

units will be flush in front with an overhang in the back as 

shown in 

Figure 2

.

3. Remove the lower front bracket from the modular unit. Retain 

the screws for later use.

4. Attach the front joining bracket to the front of the modular unit. 

Align

 

the screw holes in the bracket with the holes from the 

lower front bracket and the top panel of the coil case. See 

Figure 3

.

5. Secure the bracket with the screws removed earlier in steps 

1 & 3.

6. Attach the rear joining bracket to the backside of the modular 

unit and cased coil. Position the bracket so that it is flush with 

the sides and back of the units with the 1/2” insulation facing 

the rear gap between the units.

7. Secure the rear bracket with self tapping screws.

Downflow Installation

The MB7 Series Modular air handler may be installed in a 

downflow configuration as shown in 

Figure 1

Return air must 

enter through the top of the unit.
1. Remove the lower front bracket (

Figure 3

from the modular 

unit. Retain the screws for later use.

2. Remove the door from the cased coil and the screws (on the 

side of the cased coil) securing the lower tie bar in place. 
Retain the screws for later use. 

NOTE: 

Before mating the 

modular unit with the cased coil, clean the mating surfaces 
on both units.

3. Flip the modular unit upside down and apply the black 

neoprene gasket tape to the top of the air handler. 

NOTE:

 

The blowers flanged surface is now beneath the air handler 
and will connect with the supply air duct.

4. Carefully place the cased coil on top of the modular air handler. 

NOTE:

 Make sure the units are flush in the front and on the 

sides with a “step” fit in the back and that there are no gaps 

on the sides. See 

Figure 4 (page 7)

.

5. Attach the front joining bracket to the cased coil and the air 

handler. Align the screw holes in the bracket with the holes 

where the lower front bracket and lower tie bar were attached.

6. Secure the bracket to the modular unit and the cased coil 

with the screws removed earlier in steps 1 & 2.

7. Attach the rear joining bracket to the backside of the modular 

unit. Position the bracket so that it is flush with the sides and 

back of the units with the 1/2” insulation facing the rear gap 

between the units.

8. Secure the rear bracket to the modular unit and cased coil 

with self-tapping screws.

Horizontal Installation

MB7 air handlers are shipped from the factory ready for horizontal 

left applications and horizontal right applications. The blowers 

can be installed horizontally in an attic, basement, crawl space 

or alcove. They can also be suspended from a ceiling in a 

basement or utility room in either a right to left airflow or left 

to right airflow. A typical installation of the unit in a suspended 

horizontal application is shown in 

Figure 5 (page 7)

.

When mating the blower and coil for horizontal left or right 

applications, reference the upflow instructions on 

page  5

Make sure to account for the coil orientation by configuring the 

coil drain pan assembly properly. Multi-position procedures are 

also available in the cased coil Installation Instructions supplied 

with the unit.

Figure 3. Front Bracket Installation - (Upflow Only)

Front Joining Bra

cket

Figure 2. Rear Bracket Installation - (Upflow Only)

Rear Bra

cket

Modular Air Handler

Cased Coil

Upflow

Configuration

Upflow

Configuration

Downflow

Configuration

Figure 1. Upflow & Downflow Installation

Summary of Contents for MB7EM 3-PHASE Series

Page 1: ...ll Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury d...

Page 2: ...ion Check 10 Running the Blower Continuously 10 System Cooling 10 System Heating 10 Turning the Blower Off 10 Blower Configurations 10 Selecting Minimum Electric Heat Airflow 10 Determining Nominal Sy...

Page 3: ...s otherwise noted in these instructions only factory authorized kits or accessories may be used with this product The installer should become familiar with the units wiring diagram before making any e...

Page 4: ...gh the bottom of the unit the joint between the air handler and the return air plenum must be air tight Return air and circulating air ducts must not be connected to any other heat producing device su...

Page 5: ...nwithanoutervaporbarrier Consult your Distributor for the recommended type and thickness of insulation for your area as required by local codes Condensate Drainage CAUTION The air handler must be leve...

Page 6: ...ill connect with the supply air duct 4 Carefullyplacethecasedcoilontopofthemodularairhandler NOTE Make sure the units are flush in the front and on the sides with a step fit in the back and that there...

Page 7: ...lowerassembly The blower assembly is secured with two screws on either side near the front With these removed the blower assembly can slide out of the front of the unit Install the coil and drain pan...

Page 8: ...on delay a 15 second blower off delay in electric heat mode and a 40 second ELECTRICAL CONNECTIONS WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could res...

Page 9: ...lug of the heater kit 2 Connectthelinevoltageleadstothecircuitbreakerorterminal block provided 3 Connect the heater kit plug with the mating receptacle on the air handler control board If a heater kit...

Page 10: ...se there are so many different ways to set up the air handler it is important to read and follow these directions carefully MB7EM MB7VM air handlers use high efficiency circulating air motors that com...

Page 11: ...NG ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result in dangerous operation serious...

Page 12: ...DIMENSION E A 12 3 4 24 3 4 14 1 4 12 3 4 3 4 B 12 3 4 24 3 4 17 1 2 16 2 3 8 C 18 1 4 27 1 2 21 19 1 2 1 3 8 B A 12 7 8 E 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1...

Page 13: ...or Mount Kit Blower Motor Blower Wheel Blower Housing Transformer Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Rear Bracket Front Joining Bracket Motor Control Board Control Board F...

Page 14: ...1778 1727 1684 1613 1542 1 1 0 1 1935 1932 1884 1840 1795 1727 1659 1614 0 0 1 1 2070 2023 2009 1953 1906 1851 1800 1724 1 0 1 1 2138 2079 2063 2003 1951 1889 1830 1765 0 1 1 1 2161 2111 2091 2058 201...

Page 15: ...100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400...

Page 16: ...UIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT MB7VM 240 VAC 50 60 Hz Single Phase A 1 200 CFM 4 5 4 5 15 15 B 1 600 CFM 4 5 4 5 15 15 C 2 000 CFM 6 3 6 3 15 15 208 VAC 50 60 Hz Single Phase A 1 200...

Page 17: ...on after 15 seconds delay OFF Heat stages off instantly Blower off after 15 second delay W1 Y Y2 AUX HEAT ON 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on i...

Page 18: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Page 19: ...HEATER P1 L 2 HUM EAC P2 3A Fuse P3 EXPANSION PORT Figure 11 Two Stage Control Board All Models Figure 10 Low Voltage Wiring For Twinning Y R C Outdoor Unit A H 1 C R Y G W W G Y R Thermostat 1 A H 2...

Page 20: ...DHUM W1 THERMOSTAT EXPANSION PORT COOL HEAT FAN SPEED 1 2 3 4 5 6 7 8 OFF ON CONNECTION TERMINAL TO TWIN FURNACES GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN...

Page 21: ...RAM 3 Transformer may have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the internal wiring is replaced use only 105 C copper wire of the same gauge 3 Le transfo...

Page 22: ...ns d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Page 23: ...23...

Page 24: ...duct according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when instal...

Reviews: