background image

11

Blower Motor & Assembly

 - Inspect the blower assembly and 

motor mounting brackets for tightness and corrosion. Correct 

deficiencies if necessary. The blower motor contains sealed 

bearings and under normal operating conditions, no maintenance 

is necessary for the life of the equipment.

Cooling Coil

 - Inspect the cooling coil, drain pan, and condensate 

drain at the beginning of each cooling season for cleanliness. 

Clean these components as necessary using a mild detergent and 

water. After cleaning, flush the coil, drain pan, and condensate 

drain to remove all detergent.

IMPORTANT:

 Use caution when cleaning these components 

so that the insulation does not get wet.

TROUBLESHOOTING

If the air handler fails to operate, check the following:

•  Is the electric turned on?

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the air handler disconnect closed?

•  Has the circuit breaker tripped or the control board fuse burned 

open?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the LED on both control boards constantly ON? If not, refer 

to 

Table 2

 or 

Table 3

 to determine fault condition.

RED LED (AN2)

DIAGNOSTIC

OFF

Control Fault (No Power)

Flash

Blower Fault

ON

Normal Operation

Table 2. Air handler Control Board Fault Conditions

DIAGNOSTIC FAULT CONDITIONS

FOR VARIABLE SPEED FURNACES

GREEN

LED

RED

LED

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Communications Fault

Flash

Flash

Table 3. VSHE Motor Control Board Display Codes

UNIT MAINTENANCE

Proper maintenance is most important to achieve the best 

performance from an air handler. Some of the components 

and their locations are shown in 

Figure 8 (page 13)

. If any 

component of the air handler must be replaced, use only factory 

authorized replacement parts specified in the Replacement Parts 

List provided online.

 WARNING:

ELECTRICAL SHOCK, FIRE OR 

EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.

•  Before servicing, disconnect all electrical power 

to the indoor blower.

• When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

•  These maintenance instructions are primarily intended to assist 

qualified technicians experienced in the proper maintenance 

and operation of this appliance.

•  Always reinstall the doors on the air handler after servicing or 

cleaning/changing the filters. Do not operate the air handler 

without all doors and covers in place.

•  To achieve the best performance and minimize equipment 

failure, it is recommended that a yearly maintenance checkup 

be performed. At a minimum, this check should include the 

following items:

Air Filter(s)

 - Inspect and replace the air filter at the beginning 

of heating and cooling season. It is recommended that the filter 

be cleaned or replaced every 4 to 6 months at a minimum. Newly 

built or recently renovated homes may require more frequent 

changing until the construction dust has minimized.

 WARNING:

Never operate the air handler without a filter in 

place. Dust and lint in the return air can build 

up on internal components, resulting in loss of 

efficiency, equipment damage, and possible fire.

Filters designed to remove smaller particles such as pollen, may 

require additional maintenance.

Blower Compartment

 - Dirt and lint can create excessive 

loads on the motor resulting in higher than normal operating 

temperatures and shortened service life. It is recommended 

that the blower compartment be cleaned of dirt or lint that may 

have accumulated in the compartment or on the blower and 

motor as part of the annual inspection.

Blower Fan Wheel

 - Inspect the blower wheel blades for 

accumulations of dirt and clean if necessary. Inspect mounting 

nut for tightness.

Summary of Contents for MB7EM 3-PHASE Series

Page 1: ...ll Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury d...

Page 2: ...ion Check 10 Running the Blower Continuously 10 System Cooling 10 System Heating 10 Turning the Blower Off 10 Blower Configurations 10 Selecting Minimum Electric Heat Airflow 10 Determining Nominal Sy...

Page 3: ...s otherwise noted in these instructions only factory authorized kits or accessories may be used with this product The installer should become familiar with the units wiring diagram before making any e...

Page 4: ...gh the bottom of the unit the joint between the air handler and the return air plenum must be air tight Return air and circulating air ducts must not be connected to any other heat producing device su...

Page 5: ...nwithanoutervaporbarrier Consult your Distributor for the recommended type and thickness of insulation for your area as required by local codes Condensate Drainage CAUTION The air handler must be leve...

Page 6: ...ill connect with the supply air duct 4 Carefullyplacethecasedcoilontopofthemodularairhandler NOTE Make sure the units are flush in the front and on the sides with a step fit in the back and that there...

Page 7: ...lowerassembly The blower assembly is secured with two screws on either side near the front With these removed the blower assembly can slide out of the front of the unit Install the coil and drain pan...

Page 8: ...on delay a 15 second blower off delay in electric heat mode and a 40 second ELECTRICAL CONNECTIONS WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could res...

Page 9: ...lug of the heater kit 2 Connectthelinevoltageleadstothecircuitbreakerorterminal block provided 3 Connect the heater kit plug with the mating receptacle on the air handler control board If a heater kit...

Page 10: ...se there are so many different ways to set up the air handler it is important to read and follow these directions carefully MB7EM MB7VM air handlers use high efficiency circulating air motors that com...

Page 11: ...NG ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result in dangerous operation serious...

Page 12: ...DIMENSION E A 12 3 4 24 3 4 14 1 4 12 3 4 3 4 B 12 3 4 24 3 4 17 1 2 16 2 3 8 C 18 1 4 27 1 2 21 19 1 2 1 3 8 B A 12 7 8 E 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1...

Page 13: ...or Mount Kit Blower Motor Blower Wheel Blower Housing Transformer Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Rear Bracket Front Joining Bracket Motor Control Board Control Board F...

Page 14: ...1778 1727 1684 1613 1542 1 1 0 1 1935 1932 1884 1840 1795 1727 1659 1614 0 0 1 1 2070 2023 2009 1953 1906 1851 1800 1724 1 0 1 1 2138 2079 2063 2003 1951 1889 1830 1765 0 1 1 1 2161 2111 2091 2058 201...

Page 15: ...100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400...

Page 16: ...UIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT MB7VM 240 VAC 50 60 Hz Single Phase A 1 200 CFM 4 5 4 5 15 15 B 1 600 CFM 4 5 4 5 15 15 C 2 000 CFM 6 3 6 3 15 15 208 VAC 50 60 Hz Single Phase A 1 200...

Page 17: ...on after 15 seconds delay OFF Heat stages off instantly Blower off after 15 second delay W1 Y Y2 AUX HEAT ON 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on i...

Page 18: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Page 19: ...HEATER P1 L 2 HUM EAC P2 3A Fuse P3 EXPANSION PORT Figure 11 Two Stage Control Board All Models Figure 10 Low Voltage Wiring For Twinning Y R C Outdoor Unit A H 1 C R Y G W W G Y R Thermostat 1 A H 2...

Page 20: ...DHUM W1 THERMOSTAT EXPANSION PORT COOL HEAT FAN SPEED 1 2 3 4 5 6 7 8 OFF ON CONNECTION TERMINAL TO TWIN FURNACES GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN...

Page 21: ...RAM 3 Transformer may have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the internal wiring is replaced use only 105 C copper wire of the same gauge 3 Le transfo...

Page 22: ...ns d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Page 23: ...23...

Page 24: ...duct according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when instal...

Reviews: